Siemens SICHARGE CC AC22-MID Operating Instructions Manual page 58

Hide thumbs Also See for SICHARGE CC AC22-MID:
Table of Contents

Advertisement

Station/Power
Entering the maximum current for each outer conductor
Only a qualified electrician can make an entry in this field.
Enter the maximum available current for each phase in mA for the charging station. The
value must not exceed the rated current of the back-up fuse.
Operating two SICHARGE charging stations on one back-up fuse:
The sum of the maximum currents of both SICHARGE charging stations must not exceed the
rated current of the back-up fuse.
Setting values:
• Min. = 6000 mA
• Max. = 63000 mA or rated current of the back-up fuse if the back-up fuse is less than 63 A
Pressing the "Save" button saves the entry in the charging station.
Use the "Reload" button to retrieve and display the value from the charging station.
Figure 5-14
Station Power
SICHARGE Operating Instructions MID
Operating Instructions, 07/2020, A5E48573001-AB
WARNING
Connection and commissioning
5.5 Commissioning
57

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents