Connection Power Unit
2.6

Connection accessories

2.6.1 Filter and chokes

Voltage class
230 V
Voltage class
400 V
• The service life of the frequency converter/ servo drive with intermediate voltage circuit
depends on the current load of the electrolytic capacitors in the intermediate circuit. The
use of mains chokes can increase the service life of the condensators to a considerable
extent, especially when connecting to „hard" power systems or when under permanent
drive load (continuous duty).
For continuous duty (S1) drives with a medium duty of >60%, KEB recommends the use
of mains chokes with a terminal voltage (Uk) of 4%.
The term "hard" mains can be defined as follows:
The rated power of the inverter (Sn) is very low compared to the nodal point power
(Smains). Example:
• When using a mains choke, it should usually be mounted on the mains side of the inter-
ference suppression filter.
GB - 24
Inverter size
Filter
17
20E4T60-1001
18
22E4T60-1001
19
22E4T60-1001
20
22E4T60-1001
21
23E4T60-1001
Inverter size
Filter
18
20E4T60-1001
19
20E4T60-1001
20
20E4T60-1001
21
22E4T60-1001
22
22E4T60-1001
23
22E4T60-1001
24
23E4T60-1001
Smains
k =
––––––– >> 200
Sn
Smains
2 MVA (supply transform-
k =
––––––– = –––––––––––––––––––– = 303
Sm
Mains choke 50 Hz / 4 % Uk
17Z1B03-1000
18Z1B03-1000
19Z1B03-1000
20Z1B03-1000
21Z1B03-1000
Mains choke 50 Hz / 4 % Uk
18Z1B04-1000
19Z1B04-1000
20Z1B04-1000
21Z1B04-1000
22Z1B04-1000
23Z1B04-1000
24Z1B04-1000
er)
6.6 kVA (12.F5)
Motor choke 100 Hz / 4 % Uk
21Z1F04-1010
22Z1F04-1010
22Z1F04-1010
upon request
upon request
Motor choke 100 Hz / 4 % Uk
18Z1F04-1010
19Z1F04-1010
20Z1F04-1010
21Z1F04-1010
22Z1F04-1010
upon request
upon request
-> Choke required