Technical Data
2.2

Technical data of the 230V class

Inverter size
Housing size
Phases
Output rated power
Max. rated motor power
Output rated current
Max. short time current
OC-tripping current
Input rated current
Max. permissible main fuse gG
Rated switching frequency
Max. switching frequency
Power dissipation at nominal operating
Power dissipation at DC operating
Standstill current at 4 kHz
Standstill current at 8 kHz
Standstill current at 16 kHz
Min. frequency at continuous full load
Max. heat sink temperature
Motor cable cross-section
Min. braking resistor
Max. braking current
Overload characteristic (see annex)
Input rated voltage
Input voltage range
Input voltage at DC operation
Mains frequency
permitted mains forms
Output voltage
Output frequency
Cooling mode (L=air; W=water)
Max. motor line length shielded
1)
With the regulated systems 5% are to be subtracted as overmodulation capacity.
2)
Max. current before the OL2 function triggers (not in operating mode F5 GENERAL).
3)
Recommended minimum cross section of the motor line for rated power and a cable length of upto 100 m (copper).
4)
This data is only valid for units with internal brake transistor GTR 7 (see "Unit identification").
5)
6)
The output frequency is to be limited in such way that 1/10 of the switching frequency is not exceeded. Units with higher max. output frequency
are subject to export restrictions and are only available on request.
7)
The voltage of the motor is depending on units which are connected upstream and on the control method (example see chapter 3.3 in the annex).
8)
Protection in accordance with UL see annex "Certification".
9)
Restrictions when using HF filters.
10) Phase conductor grounded mains are only permissible without HF filters
11) with COMPACT only 8 kHz, with F6-K only 8 kHz.
The technical data are for 2/4-pole standard motors. With other pole numbers the inverter must be dimensioned onto the
motor rated current. Contact KEB for special or medium frequency motors.
17
R
3
[kVA]
33
[kW]
18.5
[A]
84
1)
[A]
126
[A]
151
[A]
92
8)
[A]
100
6) [kHz]
8
11) [kHz]
16
[W]
850
[W]
790
2)
[A]
92
2)
[A]
84
2)
[A]
50
[Hz]
3
[°C]
3)
[mm²]
35
4)
[Ω]
4.7
4)
[A]
85
[V]
[V]
[V]
[Hz]
7)
[V]
6) [Hz]
[m]
18
19
R
R
3
3
40
46
22
30
100
115
150
172
180
206
116
126
160
160
8
8
16
16
1020
1200
950
1100
110
126
100
115
70
69
3
3
90°C (194°F)
50
50
4.0
3.0
100
132
1
230 (UL: 240)
180...260 ±0
250...370 ±0
50 / 60 ±2
TN, TT, IT
, ∆-mains
9)
3 x 0...Uin
0 - max. 599
L
50
20
21
R
R
3
3
59
71
37
45
145
180
217
270
261
324
165
198
200
315
8
8
16
16
1350
1620
1230
1470
159
198
145
180
101
90
3
3
95
95
2
2
160
160
10)
GB - 13