Commissioning
3.4 Configuring the drive unit using the STARTER commissioning tool
3.4.2
Determining the component topology and configuration of the drive unit
automatically
Introduction
Once you have created the project and entered the drive unit with its bus address (e.g. 126)
ONLINE, you have to enter the associated component topology and drive unit configuration
ON
Steps
1. Select the drive unit Drive_Unit_Adr126 in the project navigator.
2. Choose Connect to target system. An ONLINE connection is established and the dialog
3. Click Close and, if necessary, restore the factory settings.
4. Select the drive unit Drive_Unit_Adr126 in the project navigator.
5. Choose Restore factory settings (see screenshot below).
Figure 3-4
6. Confirm the following queries and messages by choosing OK:
3-8
LINE.
box Online/OFFLINE comparison is displayed.
Restore factory settings
– "Restore factory settings?" dialog box
– "The factory settings have been restored" dialog box
– "The data has been successfully copied from RAM to ROM" dialog box
Commissioning Manual, 12.2004 Edition, 6SL3097-2AA00-0BP1