Commissioning
3.4 Configuring the drive unit using the STARTER commissioning tool
Example
Setting the bus address via the address switc
Figure 3-14
The following information must be taken into account!
Note
Permissible CAN bus address: 1...126.
The address setting on the switch is displayed in p8620.0.
If the switch setting is changed, the new setting does not become effective until POWER
ON.
The factory settings are "ON" or "OFF" for all switches.
While the SINAMICS S120 is being ramped up, the address switch is queried first in order to
set the bus address. If the switch setting is 0 or 127, the address can be set via parameter
p8620.0.
If the address is set to a valid node address (1...126), this is copied to parameter p8620.0
and displayed.
3-16
Example: bus address via the address switch on the Control Unit
h on the Control Unit.
Commissioning Manual, 12.2004 Edition, 6SL3097-2AA00-0BP1