Commissioning
3.4 Configuring the drive unit using the STARTER commissioning tool
3.4.7

Interconnecting the infeed

Carrying out the commissioning step
In the current software version, the infeed (Active Line Module) cannot be addressed directly
via the PDOs.
The DC link can still be activated via a signal source by means of Active Line Module
parameter p0840 (ON/OFF1), however, using the following BICO interconnection options:
• You can interconnect parameter p0840 with a free bit at the digital input of the CU320
• You can interconnect parameter p0840 with a free bit of the control word from Motor
Steps
To interconnect parameter p0840 (ON/OFF1) with the signal source (e.g. from the control
word of Motor Module 1 (Drive_1)) from the infeed, carry out the following:
1. In the project navigator, choose parameter p0840 ("search"): Infeed > right-click > Expert
2. Interconnect the p parameter with r parameter r8890 bit 15 = PZD 1 from Drive_1
3-24
(e.g. r722 bit 15).
Module 1 (e.g. r8890 bit 15).
Note
In the sample configuration describ
buffer in PZD receive word 1 (see
Note
The BICO interconnection procedure in STARTER is described in the section "BICO
interconnection procedure in STARTER".
> Expert list.
(SERVO_3).
Note
Please also refer to the commissioning instructions in the Installation and Start-Up
Manual SINAMICS S120 /IH1/
(e.g. the DC link must be activated before the Motor Module is switched on).
ed here, the control word is present at the receive
also the function diagram in the appendix).
Commissioning Manual, 12.2004 Edition, 6SL3097-2AA00-0BP1
CANopen interface