Moxa Technologies ioLogik E1200 Series User Manual page 10

Hide thumbs Also See for ioLogik E1200 Series:
Table of Contents

Advertisement

ioLogik E1200 Series
Counter/Frequency: 250 Hz, power off storage
Digital Output
I/O Mode: DO or Pulse Output
Pulse Wave Width/Frequency: 1 ms/500 Hz
Over-voltage Protection: 45 VDC
Over-current Protection: 2.6 A (4 channels @ 650 mA)
Over-temperature Shutdown: 175°C (typical), 150°C (min.)
Current Rating: 200 mA per channel
Isolation: 3K VDC or 2K Vrms
Power Requirements
Power Consumption: 140 mA @ 24 VDC
MTBF
(meantime between failures)
Time: 502,210 hrs
Database: Telcordia (Bellcore)
ioLogik E1260
RTD
Input Type: PT50, PT100, PT200, PT500, PT1000;
Resistance of 10 ohms, 20 ohms, and 100 ohms
Sampling Rate: 12 samples/sec (all channels)
Resolution: 16 bits
Accuracy:
±0.1% FSR @ 25°C
±0.3% FSR @ -10 and 60°C
Input Impedance: 625K ohms
Power Requirements
Power Consumption: 110 mA @ 24 VDC
MTBF
(meantime between failures)
Time: 660,260 hrs
Database: Telcordia (Bellcore)
ioLogik E1262
Thermocouple Input
Sensor Type: J, K, T, E, R, S, B, N
Mili Volt Type: ±78.126 mV, ±39.062 mV, ±19.532 mV
Fault and Overvoltage protection: ±35 VDC (power off); +30 VDC, -25 VDC (power on)
Sampling Rate: 12 samples/sec (all channels)
Resolution: 16 bits
Accuracy:
±0.1% FSR @ 25°C
±0.3% FSR @ -10 and 60°C
Input Impedance: 10M ohms
Power Requirements
Power Consumption: 119 mA @ 24 VDC
MTBF
(meantime between failures)
Time: 631,418 hrs
Database: Telcordia (Bellcore)