Particulate And Gaseous Contamination Specifications; Expanded Operating Temperature - Dell PowerEdge M630p Owner's Manual

Systems (vrtx enclosure)
Table of Contents

Advertisement

Table 16. Operating temperature derating specifications (continued)
Temperature
40 °C to 45 °C (104 °F to 113 °F)

Particulate and gaseous contamination specifications

The following table defines the limitations that help avoid any equipment damage or failure from particulates and gaseous contamination. If
the levels of particulates or gaseous pollution exceed the specified limitations and result in equipment damage or failure, you may need to
rectify the environmental conditions. Remediation of environmental conditions is the responsibility of the customer.
Table 17. Particulate contamination specifications
Particulate contamination
Air filtration
Conductive dust
Corrosive dust
Table 18. Gaseous contamination specifications
Gaseous contamination
Copper coupon corrosion rate
Silver coupon corrosion rate
NOTE:
Maximum corrosive contaminant levels measured at ≤50% relative humidity.

Expanded operating temperature

Table 19. Expanded operating temperature specifications
Expanded operating temperature
Continuous operation
Specifications
Maximum temperature is reduced by 1°C/125 m (1°F/228 ft)
above 950 m (3,117 ft).
Specifications
Data center air filtration as defined by ISO Class 8 per ISO 14644-1
with a 95% upper confidence limit.
NOTE:
This condition applies only to data center
environments. Air filtration requirements do not apply to
IT equipment designed to be used outside a data center,
in environments such as an office or factory floor.
NOTE:
Air entering the data center must have MERV11
or MERV13 filtration.
Air must be free of conductive dust, zinc whiskers, or other
conductive particles.
NOTE:
This condition applies to data center and nondata
center environments.
Air must be free of corrosive dust.
Residual dust present in the air must have a deliquescent point
less than 60% relative humidity.
NOTE:
This condition applies to data center and nondata
center environments.
Specifications
<300 Å/month per Class G1 as defined by ANSI/ ISA71.04-1985.
<200 Å/month as defined by AHSRAE TC9.9.
Specifications
5°C to 40°C at 5% to 85% RH with 29°C dew point.
NOTE:
Outside the standard operating temperature
(10°C to 35°C), the system can operate continuously in
temperatures as low as 5°C and as high as 45°C.
Technical specifications
19