Particulate And Gaseous Contamination Specifications - Dell W4X15 Owner's Manual

Table of Contents

Advertisement

Table 29. Maximum shock specifications
Maximum shock
Operating
Storage
Table 30. Maximum altitude specifications
Maximum altitude
Operating
Storage
Table 31. Operating temperature de-rating specifications
Operating temperature de-rating
Up to 35°C (95°F)
35°C to 40°C (95°F to 104°F)
40°C to 45°C (104°F to 113°F)

Particulate and gaseous contamination specifications

The following table defines the limitations that help avoid any equipment damage or failure from
particulates and gaseous contamination. If the levels of particulates or gaseous pollution exceed the
specified limitations and result in equipment damage or failure, you may need to rectify the
environmental conditions. Re-mediation of environmental conditions is the responsibility of the
customer.
Table 32. Particulate contamination specifications
Particulate contamination
Air filtration
Conductive dust
Specifications
Six consecutively executed shock pulses in the positive
and negative x, y, and z axes of 40 G for up to 2.3 ms.
Six consecutively executed shock pulses in the positive
and negative x, y, and z axes (one pulse on each side of
the system) of 71 G for up to 2 ms.
Specifications
3048 m (10,000 ft)
12,000 m (39,370 ft)
Specifications
Maximum temperature is reduced by 1°C/300 m (1°F/547
ft) above 950 m (3,117 ft).
Maximum temperature is reduced by 1°C/175 m (1°F/319
ft) above 950 m (3,117 ft).
Maximum temperature is reduced by 1°C/125 m (1°F/228
ft) above 950 m (3,117 ft).
Specifications
Data center air filtration as defined by ISO Class 8 per ISO
14644-1 with a 95% upper confidence limit.
NOTE: This condition applies to data center
environments only. Air filtration requirements do not
apply to IT equipment designed to be used outside a
data center, in environments such as an office or
factory floor.
NOTE: Air entering the data center must have
MERV11 or MERV13 filtration.
Air must be free of conductive dust, zinc whiskers, or
other conductive particles.
41