Specifications - Altronix LINQ8ACM Installation And Programming Manual

Dual input network access power controllers
Table of Contents

Advertisement

Altronix LINQ8ACM(CB) are dual input network access power controllers which can be installed in Altronix wall
and rack mount enclosures to facilitate access control deployment. Access Power Controller's dual input design
allows power to be steered from one (1) or two (2) independent low voltage 12 or 24 VDC Altronix power supplies
to eight (8) independently controlled fuse (LINQ8ACM) or PTC (LINQ8ACMCB) protected outputs. Outputs are
activated by an open collector sink, normally open (NO), normally closed (NC) dry trigger input, or wet output
from an Access Control System, Card Reader, Keypad, Push Button, PIR, etc. LINQ8ACM(CB) will route power
to a variety of access control hardware devices including Mag Locks, Electric Strikes, Magnetic Door Holders,
etc. Outputs will operate in both Fail-Safe and/or Fail-Secure modes. The FACP Interface enables Emergency
Egress, Alarm Monitoring, or may be used to trigger other auxiliary devices. The fire alarm disconnect feature
is individually selectable for any or all of the eight (8) outputs. The spade connectors allow you to daisy chain
power to multiple LINQ8ACM(CB) modules. This feature allows you to distribute the power over more outputs
for larger systems. Built-in LINQ
of power/diagnostics.
Input Voltage Options:
• Single Input:
Input1: 12 or 24 VDC from eFlow series power supply.
• Dual Input Option 1:
- Input 1: 12 or 24 VDC from eFlow series power supply.
- Input 2:
a - 12 or 24 VDC from eFlow series power supply.
b - 5 or 12 VDC from VR6 voltage regulator.
• Dual Input Option 2: 24 and 12 VDC from Tango1B PoE Driven Power Supply.
• Input Current:
LINQ8ACM:
LINQ8ACMCB: 16A total.
• Eight (8) trigger inputs:
a) Normally open (NO) inputs (dry contacts).
b) Normally closed (NC) inputs (dry contacts).
c) Open collector sink inputs.
d) Wet Input (5VDC - 24VDC) with 10K resistor.
e) Any combination of the above.
Outputs:
• LINQ8ACM:
Fuse protected outputs rated @ 2.5A per output, non power-limited. Total output 20A max.
LINQ8ACMCB:
PTC protected outputs rated @ 2A per output, Class 2 power-limited. Total output 16A max.
Do not exceed the individual power supply ratings.
See Input/Output Voltage Ratings, pg. 6.
See Maximum Output of Altronix Power Supplies.
• Eight (8) selectable independently controlled outputs (see below for ratings):
a) Fail-Safe and/or Fail-Secure power outputs.
b) Auxiliary power outputs (unswitched).
c) Any combination of the above.
• Individual outputs may be set to OFF position for servicing (output jumper set to middle position).
• Any of the eight (8) fuse/PTC protected power outputs are selectable to follow power Input 1 or Input 2.
Output voltage of each output is the same as the input voltage of the input selected.
See Input/Output Voltage Ratings, pg. 6.
• Surge suppression.
Programmable Features:
• Eight (8) programmable outputs:
- Fail-safe, fail-secure or auxiliary outputs.
- Input controlled or manually controlled through software.
- High (over) and low (under) voltage and current monitoring by output.
- Multiple outputs may be programmed to be triggered by a single input.
- Battery back-up by output.