Altronix LINQ8ACM Installation And Programming Manual page 5

Dual input network access power controllers
Table of Contents

Advertisement

Terminal/Legend
A B C D E F G H I
– PWR1 +
A B C D E F G H I
– PWR2 +
Output LED
Output Jumper
COM –
Output 1 through
J K L M N O P Q R S T U V W X Y Z
Output 8
NO, C, NC, COM
J K L M N O P Q R S T U V W X Y Z
– F, + F
J K L M N O P Q R S T U V W X Y Z
– R, + R
J K L M N O P Q R S T U V W X Y Z
GND, EOL
J K L M N O P Q R S T U V W X Y Z
GND, RST
J K L M N O P Q R S T U V W X Y Z
C, NC
+ PS1 –
+ BAT –
+ PS2 –
+ BAT –
+ INP1 – through
+ INP8 –
Tamper
AC / NC, C
BAT / NC, C
8-Pin Connector
USB
RJ45
PWR1+, PWR2+ Positive [+] plugs for spade connectors.
2-Pin Connector
LINQ8ACM(CB)
Terminal/Connector Identification:
Description
J K L M N O P Q R S T U V W X Y Z
First DC power supply input.
J K L M N O P Q R S T U V W X Y Z
Second DC power supply input.
J K L M N O P Q R S T U V W X Y Z
Individual output voltage LEDs. 12VDC (Green) or 24VDC (Red).
J K L M N O P Q R S T U V W X Y Z
Individual output voltage selection jumper.
J K L M N O P Q R S T U V W X Y Z
Common Negative [–] plug for spade connectors.
Eight (8) selectable independently controlled outputs [Fail-Safe (NC) or
Fail-Secure (NO)].
FACP Signaling Circuit Input terminals. Class 2 power-limited.
FACP Signaling Circuit Return terminals. Class 2 power-limited.
EOL Supervised FACP Input terminals for polarity reversal FACP function.
Class 2 power-limited.
FACP interface latching or non-latching. NO dry input. Class 2 power-limited.
To be shorted for non-latching FACP interface or Latch FACP reset.
FACP Dry NC output rated 1A/28VDC @ 0.6 Power Factor. Class 2 power-limited.
With EOL JMP intact, will provide 10k resistance in a normal state.
Connection to [+ BAT –] terminals of Power Supply 1.
Connection to stand-by battery(ies) for Power Supply 1.
Connection to [+ BAT –] terminals of Power Supply 2.
Connection to stand-by battery(ies) for Power Supply 2.
Eight (8) independently controlled Normally Open (NO), Normally Closed (NC),
Open Collector Sink or Wet Input Triggers.
Tamper Switch Input.
Connect appropriate signaling notification devices to the terminals to report AC fail.
Connect appropriate signaling notification devices to the terminals to report battery fail.
Reserved for future use.
Reserved for future use.
For connection to VR6 or Tango1B.
Laptop connection enables LINQ8ACM(CB) initial setup and programming.
Ethernet: LAN or laptop connection enables LINQ8ACM(CB) programming and
status monitoring.
Connection to [AC Fail] terminals on power supply.
- 5 -

Advertisement

Table of Contents
loading

This manual is also suitable for:

Linq8acmcb

Table of Contents