Table of Contents: MaximalD Series Overview ..................... 3 MaximalD Series Configuration Chart ................3 MaximalD Series Features ....................3 MaximalD Installation Instructions ................4-5 Maintenance ........................5 Power Supply Board LED Diagnostics ................5 Access Power Controller LED Diagnostics ..............6 Power Supply Board Terminal Identification ..............
MaximalD Installation Instructions: Wiring methods shall be in accordance with the National Electrical Code/NFPA 70/ANSI, and with all local codes and authorities having jurisdiction. Product is intended for indoor use only. Power Supply Board LED Diagnostics (pg. 5) Access Power Controller LED Diagnostics (pg.
9. FACP Dry form “C” output (Fig. 2a, pg. 8): FACP form “C” contacts can be use to trigger reporting or signaling devices. These contact switch upon a fire alarm input trigger to the ACM8CB boards. 10. Stand-by Battery Connections (Figs. 3-7, pgs. 9-13): For Access Control applications batteries are optional.
Power Supply Board LED Diagnostics: Red (Bat) Battery Status Normal operating condition. Battery fail/low battery. Access Power Controller LED Diagnostics: LED 1- LED 8 (Red) Output relay(s) energized. Output relay(s) de-energized. Trg (Green) FACP input triggered (alarm condition). FACP normal (non-alarm condition). Power Supply Board Terminal Identification: Terminal Function/Description...
Access Power Controller Typical Application Diagram (for each ACM8CB): Fig. 2 Fig. 2a KEYPAD ACCESS CONTROL PANEL PUSH FACP BUTTON FACP Dry Form "C" (Fire Output OUTPUT Alarm RELAY Control Panel) IN GND IN GND IN GND IN GND IN GND IN GND IN GND IN GND...
Fig. 3 Maximal3D Tamper Switch Maximal5D Wire Strap (from Enclosure Power Supply Board to Door) BAT FAIL AC FAIL NO C NC NO C NC 115VAC Input Line Neutral 60 Hz. Earth Ground *12VDC operation: For 12VDC operation only a single battery is needed. Connect red battery lead to terminal marked [+ BAT] and to the [positive (+)] terminal of the...
Fig. 4 Maximal7D Tamper Switch Power Supply Board BAT FAIL AC FAIL NC C NO NC C NO AC DELAY 115VAC Input Line Neutral 60 Hz. Earth Ground 12VDC Rechargeable 12VDC Rechargeable Battery** Battery** (Optional) (Optional) **24VDC operation: Connect two (2) 12VDC batteries in series Fig.
NEC Power-Limited Wiring Requirements for Maximal3D: Power-limited and non power-limited circuit wiring must remain separated in the cabinet. All power-limited circuit wiring must remain at least 0.25” away from any non power-limited circuit wiring. Furthermore, all power-limited circuit wiring and non power-limited circuit wiring must enter and exit the cabinet through different conduits. One such example of this is shown below.
NEC Power-Limited Wiring Requirements for Maximal5D: Power-limited and non power-limited circuit wiring must remain separated in the cabinet. All power-limited circuit wiring must remain at least 0.25” away from any non power-limited circuit wiring. Furthermore, all power-limited circuit wiring and non power-limited circuit wiring must enter and exit the cabinet through different conduits. One such example of this is shown below.
NEC Power-Limited Wiring Requirements for Maximal7D: Power-limited and non power-limited circuit wiring must remain separated in the cabinet. All power-limited circuit wiring must remain at least 0.25” away from any non power-limited circuit wiring. Furthermore, all power-limited circuit wiring and non power-limited circuit wiring must enter and exit the cabinet through different conduits. One such example of this is shown below.
FACP Hook-up Diagrams: Fig. 8 Polarity reversal input from FACP signaling circuit output (polarity is referenced in alarm condition): JUMPER J3 FACP SIGNAL CIRCUIT OUTPUT EOL FROM FACP SIGNAL OUTPUT CIRCUIT Fig. 9 Normally Open - Non-Latching FACP Fig. 10 Normally Open FACP Latching trigger input trigger input: with reset: (This output has not been evaluated by UL)
Enclosure Dimensions (H x W x D approximate) 27” x 19” x 6.25” (685.8mm x 482.6mm x 158.75mm) 19” (482.6mm) 2” 4” 4” 7” 1.25” (50.8mm) (101.6mm) (101.6mm) (177.8mm) (31.75mm) 6.25” (158.75mm) 6.25” 10.76” (158.75mm) (273.3mm) 1.25” 0.85” 0.85” (31.75mm) (21.6mm) (21.6mm) 2.5”...
Page 16
Notes: Altronix is not responsible for any typographical errors. 140 58th Street, Brooklyn, New York 11220 USA, 718-567-8181, fax: 718-567-9056 web site: www.altronix.com, e-mail: info@altronix.com, Lifetime Warranty, Made in U.S.A. MEMBER IIMaximal3D/5D/7D Series B04O - 16 - Maximal3D/Maximal5D/Maximal7D Access Power Controllers (PTC)