Declaration Of Safety Conformity And Ce Marking; Inquiries; Operation - ABB PowerValue 11 RT G2 User Manual

Hide thumbs Also See for PowerValue 11 RT G2:
Table of Contents

Advertisement

1 I M P O R TA N T S A F E T Y I N S T R U C T I O N S

1 .3 Declaration of safety conformity and CE marking

The PowerValue 11 RT G2 1-3 kVA is designed,
manufactured and commercialized in accordance
with the EN ISO 9001 standard relating to quality
management systems.
These products conform with the
following directives:
• 2014/35/EU Low voltage directive
• 2014/30/EU Electromagnetic Compatibility
directive (EMC)
• 2011/65/EU Restriction of the use of certain
hazardous substances (RoHS) directive
WARNING

1 .4 Inquiries

Inquiries regarding the UPS should be
addressed to the local ABB office or agent
authorized by ABB. Note the type code and
the serial number of the equipment before

1 .5 Operation

WARNING
NOTE
NOTE
THIS IS A CATEGORY C2 UPS PRODUCT. IN
A RESIDENTIAL ENVIRONMENT, THIS
PRODUCT MAY CAUSE RADIO
INTERFERENCE, IN WHICH CASE THE USER
MAY BE REQUIRED TO TAKE ADDITIONAL
MEASURES.
DO NOT DISCONNECT THE MAINS CABLE
FROM THE UPS OR THE BUILDING WIRING
SOCKET DURING OPERATION AS THIS
REMOVES THE GROUND FROM THE UPS
AND ALL CONNECTED LOADS.
PRESS THE OFF BUTTON TO FULLY
DISCONNECT THE UPS. ENSURE THE UPS IS
ON BYPASS OR ON STANDBY MODE BEFORE
DISCONNECTING IT FROM THE MAINS.
TO REDUCE THE RISK OF FIRE, CONNECT
THE UPS TO A CIRCUIT PROVIDED WITH
BRANCH CIRCUIT OVERCURRENT
PROTECTION WITH AN AMPERE RATING IN
ACCORDANCE WITH THE IEC/EN 60934
STANDARD OR YOUR LOCAL ELECTRICAL
CODE.
SEE TECHNICAL SPECIFICATIONS FOR
RECOMMENDATIONS.
These products also meet the following
product standards:
Table 1: Standards
Product Standards
ESD
IEC 61000-4-2 Level 3
IEC 61000-2-2
Low Frequency Signals
Disturbing Voltage:10V
RS
IEC61000-4-3 Level 3
EFT
IEC 61000-4-4 Level 4
Surge
IEC 61000-4-5 Level 4
CS
IEC 61000-4-6 Level 3
Power Frequency Magnetic
IEC 61000-4-8 Level 4
Field Immunity
Conducted
IEC 62040-2 Category C2
Radiated
IEC 62040-2 Category C2
Performance classification
VFI-SS-III
Safety
IEC 62040-1:2008+A1+2013
Transportation
IEC 60068-2-31
IEC 60068-2-64
IEC 60068-2-27
contacting ABB or authorized agent. The
serial number is shown on the nameplate
of the product. For further information on
troubleshooting, see Chapter 6.
INDISCRIMINATE OPERATION OF
SWITCHES MAY CAUSE OUTPUT LOSS
OR DAMAGE TO EQUIPMENT.
WARNING
NEVER DISPOSE OF BATTERIES IN A FIRE
AS THEY MAY EXPLODE.
WARNING
DO NOT OPEN OR DAMAGE
THE BATTERIES.
WARNING
RELEASED ELECTROLYTE IS HARMFUL
TO THE SKIN AND EYES.
WARNING
5