24
A B B U P S P R O D U C T S A N D S O L U T I O N S
08: Bypass voltage range setting
Interface
09: Bypass frequency range settings
Interface
Settings
HLS: Bypass high voltage point
245-276: Sets the high voltage point in parameter 1 from 245 Vac to 276 Vac
(Default: 264 Vac)
VAC
LLS: Bypass low voltage point
120-215: Sets the low voltage point in parameter 1 from 120 Vac to 215 Vac
(Default: 184 Vac)
VAC
Settings
H
z
Parameter 1: Set the acceptable high frequency point and low voltage point for Bypass
mode by pressing the Down key or Up key
HLS: Bypass high frequency point
51.0-54.0: Sets the high frequency point in parameter 1 from 51.0 Hz to 54.0 Hz for 50 Hz
system. (Default: 54.0 Hz)
61.0-64.0: Sets the high frequency point in parameter 1 from 61.0 Hz to 64.0 Hz for 60 Hz
system. (Default: 64.0 Hz)
H
z