03: Output frequency settings
Interface
04: ECO enable/disable
Interface
05: ECO voltage range settings
Interface
Settings
Parameter 1: Output frequency setting.
You may set the initial frequency on battery mode:
H
z
50: output frequency is 50 Hz
60: output frequency is 60 Hz
If converter mode is enabled, you may choose from the following output frequency:
50: output frequency is 50 Hz
60: output frequency is 60 Hz
Settings
Parameter 1: Output voltage
VAC
You may choose the following output voltage:
208: output voltage is 208 Vac
220: output voltage is 220 Vac
230: output voltage is 230 Vac (default)
240: output voltage is 240 Vac
Settings
%
Parameter 1: Set the acceptable high voltage point and low voltage point for ECO mode
by pressing Down key or Up key
HLS: High loss voltage in ECO mode in parameter 1.
The setting range in parameter 1 is from 5% to 10% of the nominal voltage.
(Default: 5%)
%
LLS: Low loss voltage in ECO mode in parameter 1.
The setting range in parameter 1 is from -5% to -10% of the nominal voltage.
(Default: -5%)
%