Omron FZ3 Series User Manual page 190

Vision sensor
Table of Contents

Advertisement

Note
When the communication specification "Output Control" is set to "Synchronization output", levels will be
counted according to the number of times the STEP signal turns on. For this reason, perform settings so that
results are output only once for each measurement.(1 unit for [Judgement Output], 1 data item for [Data Output])
Reference:
Only designate the STEP signal for measurement command input.
When measurement and continuous measurement are performed using serial commands, the output time will
not match and this can cause controller malfunctions.
Example) Stepped transmission line utilizing star wheel
The discharge timing for when a defective part is found and the measurement results output timing can
be synchronized.
6
Inputting a measurement trigger in the STEP signal
Example) When "2" is set for "Number of delay"
188
Controlling/Outputting through Parallel Communication
Setting Communication Specifications (Parallel Interface) (p.178)
FZ3 User's Manual