Advertisement

Wiring
The repeater panels are designed to be
wired in a fault tolerant (fail safe) loop
configuration, from comms A to B and
back to the main panel again (see diagram).
This enables repeater panels to still work if
there is a break in the cables.
If replacing an older system where the
existing cabling cannot be configured in
a loop as shown, it is possible to change
the panel back to radial circuit comms
monitoring. See panel wide settings 2-1-
2-3 option 6 (Repeater Comms Monitoring Type).
4
4
4
3
Programming of all the repeater panels is done from the main control panel.
The repeater panels have 2 inputs located on the main circuit board, Class Change (CC) and Alert (PUL).
Switching a negative voltage into these inputs will cause the alarm sounders to operate. The Class Change
input (CC) will cause the alarms to sound continously and the Alert input (PUL) will cause the alarms to
pulse.
There are also 6 switch -ve outputs located on the Comms PCB. By default o/p 1 is set to activate on
common fire and o/p 2 is set to activate for common fault.
There are 4 programming options available for the inputs and outputs in the repeater panels.
Outputs 1 - 6 activate on common fire
Outputs 1 - 6 activate zonally for zones 1 - 6
Outputs 1 - 6 activate zonally for zones 7 - 12
Change inputs CC & PUL to power supply fault inputs.
It is also possible in this programming mode to disable the controls on repeater panels, making them
passive instead of active and to disable the battery monitoring on the repeater panel if no battery backup
is required.
Enter the above code and press ENTER. The zone 1 fire LED will light. This indicates which repeater panel
is to be programmed 1 - 8. Use button 1 to move the fire zone LED to the required repeater.
With the required repeater for editing LED lit, press the ENTER button to enter 'editing mode'. The fire zone
1 LED will now pulse to indicate setting of attribute 1 (outputs 1 - 6 common fire) for that repeater.
Use button 1 to scroll to the attribute that requires editing, inidicated by a pulsing fire LED 1 - 7 as per
table below. Now use button 2 to change the setting indicated by the amber, fault LEDs, ON or OFF. Then
use button 1 again to move to the next attribute if required. See repeater instruction manual for further
details of option 7
Fire LED (pulsing)
LED 1
O/P 1 - 6
Attribute
Common Fire
Default Setting
OFF
Esento Marine 8-12 Installation, Commissioning & Operating Manual
Programming Repeater Panels
LED 2
LED 3
O/P 1 - 6
O/P 1 - 6
Zonal (Zones
Zonal (Zones
1 - 6)
7 - 12)
OFF
OFF
SETUP & PROGRAMMING
Fault Tolerant Loop Wiring
COMS A
COMS B
28
SW -ve OUTPUTS
COMS A
+ - + -
1
2
3
4
5
6
+ - + -
V+
ON
1
2
3
4
ADDRESS
Main Panel
Repeater/Network Panel 1
LED 4
Inputs For
PSU Fault
OFF
Approved Document Ref: UI-ESEN12MAR-01 Issue 8.0
47
COMS B
28
SW -ve OUTPUTS
COMS A
COMS B
1
2
3
4
5
6
+ - + -
V+
ON
1
2
3
4
ADDRESS
Repeater/Network Panel 2
LED 5
LED 6
Controls
Disable Battery
Passive
Monitoring
OFF
OFF
28
SW -ve OUTPUTS
1
2
3
4
5
6
V+
ON
1
2
3
4
ADDRESS
LED 7
Repeater
Mimic Display
Mode
OFF