Haes ESENTO ESEN-8MAR Installation, Commissioning & Operating Manual page 44

Marine approved 8 - 12 zone conventional control panel
Table of Contents

Advertisement

SETUP & PROGRAMMING
4
2
2
4
The Fire relays and switched negative outputs in the panel will, by default, activate continuously for any
fire condition from the entire network.
The Fault relay and other switched negative outputs will also activate continuously, by default, if they have
been made programmable using programming option 4-1-4-2.
This option enables the default to be changed for each of the local relays and outputs. The response can
be either; CONTINUOUS, PULSING or NONE when a fire condition is received from any other panel in the
network.
Enter the above code and press the ENTER button.
The zone 1 fire LED will pulse indicating setting the response for the Fire
relay on the main PCB.
The relays and outputs are represented by zone LEDs 1 - 10 as per table
below.
A pulsing red fire LED indicates which relay or output is selected and the setting is represented by the
amber fault LED. See tables below.
Use button 1 to move the pulsing fire LED to the required relay or output, then use button 2 to change
the response, indicated by the amber fault LED. Each press of button 2 will toggle through the 3 available
responses.
LED 1
LED 2
LED 3
Fire
Fault
Fire O/P
Relay
Relay
(Main
(Main
(Main
PCB)
PCB)
PCB)
Amber LED ON
Amber LED PULSING
Amber LED OFF
When finished, press and hold Button 1 for 3 seconds to save setting and exit programming mode.
Note:- The relay and output responses to a fire condition from their own panel are set using programming
option 4-2-4-2.
If a local response has been programmed, consideration should also be given to the network response
which may affect it.
Esento Marine 8-12 Installation, Commissioning & Operating Manual
Output & Relay Network Responses
RESOUND
SILENCE
RESET
1
2
3
4
Disable
Test
Mute
Test
Mode
Mode
Buzzer
Lamps
LED 4
LED 5
Fault
OPA
O/P
Zone
(Main
ext card
PCB)
1 (Zones
5 - 8)
Relay/output activates CONTINUOUSLY for other network panel fires
Relay/output PULSES for other network panel fires
Relay/output NO RESPONSE for other network panel fires
RESOUND
1
2
ENTER
Disable
Test
Mode
Mode
LED 6
LED 7
OPB
Aux
Zone
Relay
ext card
Zone
1 (Zones
ext card
5 - 8)
1 (Zones
5 - 8)
Approved Document Ref: UI-ESEN12MAR-01 Issue 8.0
42
RESOUND
SILENCE
RESET
1
2
3
4
Disable
Test
Mute
Test
Mode
Mode
Buzzer
Lamps
SILENCE
RESET
3
4
ENTER
Mute
Test
Buzzer
Lamps
LED 8
LED 9
LED 10
OPA
OPB
Aux
Zone
Zone
Relay
ext card
ext card
Zone
2 (Zones
2 (Zones
ext card
9 - 12)
9 - 12)
2 (Zones
9 - 12)
ENTER

Hide quick links:

Advertisement

Table of Contents
loading

This manual is also suitable for:

Esento esen-12mar0832-med-1086

Table of Contents