Haes ESENTO ESEN-8MAR Installation, Commissioning & Operating Manual page 41

Marine approved 8 - 12 zone conventional control panel
Table of Contents

Advertisement

4
3
4
2
Conventional Sounder Circuit Responses to Selected Zones
Each of the conventional sounder circuits on the main circuit board and high spec zone extension cards
can be independently programmed to respond in one of three different ways for each zone, ON, OFF or
PULSING.
Enter the above code and press the ENTER button.
The zone 1 fire LED will light. This indicates setting how each of the
sounder circuits are to respond for zone 1.
The amber, fault LEDs will show the current sounder circuit settings for
that zone. See table below
RESOUND
SILENCE
1
2
Disable
Test
Mute
Mode
Mode
Buzzer
The fire zone 1 LED will now pulse to indicate setting the response of the first sounder circuit (SNDR1 on
main circuit board) for the selected zone.
Use button 1 to scroll to the sounder circuit that requires editing, inidicated by a pulsing fire LED 1 - 6 as
per table below.
The setting of the sounder circuit is indicated by the amber, fault LED, ON, OFF or PULSING.
LED 1
LED 2
SNDR1
SNDR2
(Main
(Main
PCB)
PCB)
Use button 2 to change the response of the sounder circuit for the
selected zone, ON, OFF or PULSING, indicated by the amber, fault
LED, then use button 1 to move to the next output if required.
Tip - You can use button 4 to change the response of all sounder
circuits simultaneously to ON, OFF or PULSING (for faster
programming).
RESOUND
SILENCE
1
2
3
4
Disable
Test
Mute
Test
Mode
Mode
Buzzer
Lamps
When finished, press and hold Button 1 for 3 seconds to save setting and exit programming mode
Enter the next programming code or disable the controls and return DIL switch 6 to 'OFF'.
Esento Marine 8-12 Installation, Commissioning & Operating Manual
Use button 1 to move to the zone that requires editing.
RESET
With the required zone for editing LED lit, press the ENTER
button to enter 'editing mode'.
3
4
ENTER
Test
Lamps
LED 3
SNDR A.
Zone ext card
1 (Zones 5
- 8)
RESET
Press the ENTER button to return back to the zone selection, indicated
by a steady zone fire LED
ENTER
SETUP & PROGRAMMING
LED 4
LED 5
SNDR B.
SNDR A.
Zone ext card
Zone ext card
1 (Zones 5
2 (Zones 9 -
- 8)
12)
Approved Document Ref: UI-ESEN12MAR-01 Issue 8.0
39
RESOUND
SILENCE
RESET
1
2
3
4
Disable
Test
Mute
Test
Mode
Mode
Buzzer
Lamps
LED 6
SNDR B.
Zone ext card
2 (Zones 9 -
12)
RESOUND
SILENCE
RESET
1
2
3
4
Disable
Test
Mute
Test
Mode
Mode
Buzzer
Lamps
ENTER
ENTER