Haes ESENTO ESEN-8MAR Installation, Commissioning & Operating Manual page 26

Marine approved 8 - 12 zone conventional control panel
Table of Contents

Advertisement

PAGE HEADER
2
1
2
3
There are 11 general, panel wide, settings available.
Enter the above code and press the ENTER button. The 11 programmable
options are represented by fire zone LEDs 1 - 11.
Use button 1 to move to option required as per table;
RESOUND
SILENCE
1
2
3
Disable
Test
Mute
Mode
Mode
Buzzer
OPTION 1.
Change / Remove Keypad Access Code
The keypad can be used to activate the panel controls instead of using the key switch. The default code
is 1-2-3-4, however, this can be changed. It is also possible to disable the use of a code entry to enable
controls, forcing the use of the key switch only.
With the zone 1 fire LED lit, press the ENTER button. Zone 1 fire LED will pulse to indicate 'edit mode' and
the amber, fault LEDs will start to rapidly pulse in sequence to show the currently set code.
Enter the new code slowly and deliberately, one number at a time using buttons 1 - 4
Note: Enable Controls codes must always start with a 1 or 2.
When finished entering the new four digit code, press the ENTER button. The panel will then confirm the
new code with rapidly pulsing LEDs in sequence and zone 1 fire LED will return to steady 'view mode'.
Changing the keypad code to 1 - 1 - 1 - 1 will disable the use of a keypad to enable controls.
Press button 1 to move to next option or hold button 1 for 3
seconds to exit programming mode 2-1-2-3. (The panel will
confirm the new access code one more time before exiting the
programming mode).
Esento Marine 8-12 Installation, Commissioning & Operating Manual
Panel Wide Settings
Fire LED
1
RESET
2
4
3
ENTER
4
Test
Lamps
5
6
7
8
9
10
11
Programming Option
Change / remove keypad access code
Set number of repeater panels on system
Set time for panel delay timer (1 - 10 minutes)
UPS Mode / Disable battery monitoring
Setup internal PCB configuration (adding or removing
extension zone cards)
Change network/repeater comms monitoring type
Set number of output cards
Inhibit muted tone beeps
Inhibit network alarms & faults for panel
Set number of network slave panels on system
Inhibit fire & fault buzzer on network slave panel
Approved Document Ref: UI-ESEN12MAR-01 Issue 8.0
24
RESOUND
SILENCE
RESET
1
2
3
4
Disable
Test
Mute
Test
Mode
Mode
Buzzer
Lamps
RESOUND
SILENCE
RESET
1
2
3
4
Disable
Test
Mute
Test
Mode
Mode
Buzzer
Lamps
ENTER
ENTER

Hide quick links:

Advertisement

Table of Contents
loading

This manual is also suitable for:

Esento esen-12mar0832-med-1086

Table of Contents