Haes ESENTO ESEN-8MAR Installation, Commissioning & Operating Manual page 45

Marine approved 8 - 12 zone conventional control panel
Table of Contents

Advertisement

4
3
2
4
Sounder Circuit Network Responses
The six possible sounder circuits in the panel will, by default, activate continuously for any fire condition
from the entire network.
This option enables the default to be changed for each of the local circuits. The response can be either;
CONTINUOUS, PULSING or NONE when a fire condition is received
from any other panel in the network.
Enter the above code and press the ENTER button.
The zone 1 fire LED will pulse indicating setting the response for sounder
circuit 1.
Sounder circuits 1 - 6 are represented by zone LEDs 1 - 6 respectively.
A pulsing red fire LED indicates which circuit is selected and the setting is represented by the amber fault
LED as per table below.
Use button 1 to move the pulsing fire LED to the required circuit, then use button 2 to change the response
of the circuit, indicated by the amber fault LED. Each press of button 2 will toggle through the 3 available
responses.
LED 1
LED 2
SNDR1
SNDR2
(Main
(Main
PCB)
PCB)
Amber LED ON
Amber LED PULSING
Amber LED OFF
Esento Marine 8-12 Installation, Commissioning & Operating Manual
LED 3
LED 4
SNDR A.
SNDR B.
Zone ext card
Zone ext card
1 (Zones 5
1 (Zones 5
- 8)
- 8)
Sounder circuit activates CONTINUOUSLY for other network panel fires
Sounder circuit PULSES for other network panel fires
Sounder circuit NO RESPONSE for other network panel fires
SETUP & PROGRAMMING
LED 5
SNDR A.
Zone ext card
2 (Zones 9 -
12)
Approved Document Ref: UI-ESEN12MAR-01 Issue 8.0
43
RESOUND
SILENCE
RESET
1
2
3
4
Disable
Test
Mute
Test
Mode
Mode
Buzzer
Lamps
LED 6
SNDR B.
Zone ext card
2 (Zones 9 -
12)
ENTER