Haes ESENTO MARINE Installation, Commissioning & Operating  Manual

Haes ESENTO MARINE Installation, Commissioning & Operating Manual

Marine approved 2 - 4 zone conventional control panel

Advertisement

MARINE APPROVED 2 - 4 ZONE CONVENTIONAL
CONTROL PANEL
Installation, Commissioning &
Operating Manual
MED Ref: 0832/15
Approved Document UI-ESEN4MAR-01 Issue 6.0

Advertisement

Table of Contents
loading
Need help?

Need help?

Do you have a question about the ESENTO MARINE and is the answer not in the manual?

Questions and answers

Subscribe to Our Youtube Channel

Summary of Contents for Haes ESENTO MARINE

  • Page 1 MARINE APPROVED 2 - 4 ZONE CONVENTIONAL CONTROL PANEL Installation, Commissioning & Operating Manual MED Ref: 0832/15 Approved Document UI-ESEN4MAR-01 Issue 6.0...
  • Page 2 Haes Technologies Ltd, Unit 3, Horton Industrial Park, West Drayton, UB7 8JD Model Number MED Ref No. Esento Marine 2-4 zone conventional panel ESEN-2MAR/4MAR 0832-MED-1086 European Standard EN54-2 : 1997 + A1 : 2006 Control and indicating equipment for fire detection and fire alarm systems for buildings.
  • Page 3: Table Of Contents

    SERVICE & MAINTENANCE THE NEED FOR MAINTENANCE DUTIES OF THE RESPONSIBLE PERSON ROUTINE MAINTENANCE & TESTING SCHEDULE OF TESTING LOG BOOK FALSE ALARMS, FAULTS & ENGINEER VISIT LOG BOOK Esento Marine 2-4 Installation, Commissioning & Operating Manual Approved Document UI-ESENMAR-01 Issue 6.0...
  • Page 4: About This Panel

    ABOUT THIS PANEL PRODUCT OVERVIEW The Esento Marine 2 or 4 zone is a conventional control panel with integral power supply & space for standby batteries. Esento Marine panels are fully approved to European standards EN54-2 & 4, Fire Detection and Alarm Systems –...
  • Page 5 ABOUT THIS PANEL CABINET 80mm 57mm Fire Detection System 260mm 308mm 250mm 300mm Esento Marine 2-4 Installation, Commissioning & Operating Manual Approved Document UI-ESENMAR-01 Issue 6.0...
  • Page 6: Circuit Boards

    ABOUT THIS PANEL CIRCUIT BOARDS Esento Marine 2-4 zone panels comprise of two circuit boards TPCA01-E2MAR/E4MAR - 2 or 4 zone Master PCB 28V 0V FIRE FAULT SNDR1 SNDR2 ZONE1 ZONE2 ZONE3 ZONE4 + - + - C NC NO...
  • Page 7: Main Pcb Terminals

    Relay Coil 28V 0V FIRE FAULT SNDR1 SNDR2 ZONE1 ZONE2 ZONE3 ZONE4 + - + - C NC NO C NC NO -OP -OP -IP -IP BATTERY Esento Marine 2-4 Installation, Commissioning & Operating Manual Approved Document UI-ESENMAR-01 Issue 6.0...
  • Page 8: Technical Specification

    IEC 60068-2-6 Test F Inclination IEC 60092-501 22.5 Number of conventional detection circuits 2 or 4 Detector compatibility Apollo: S65, Orbis. / Hochiki CDX. / Nittan EV Esento Marine 2-4 Installation, Commissioning & Operating Manual Approved Document UI-ESEN4MAR-01 Issue 6.0...
  • Page 9: Power Supply Module

    Resistance = 1 Ohm or greater 1 hour reporting time Max current drawn from batteries 1.5 Amps with main power source disconnected. Battery fuse 3A LBC 20mm. Esento Marine 2-4 Installation, Commissioning & Operating Manual Approved Document UI-ESENMAR-01 Issue 6.0...
  • Page 10: Design Considerations

    DESIGN CONSIDERATIONS TYPICAL DETECTION CIRCUIT SCHEMATIC Esento Marine 2-4 Installation, Commissioning & Operating Manual Approved Document UI-ESEN4MAR-01 Issue 6.0...
  • Page 11 DESIGN CONSIDERATIONS TYPICAL SOUNDER CIRCUIT SCHEMATIC 4K7 OHM END OF LINE RESISTOR MOTORISED BELL POLARISED MOTORISED BELL POLARISED ELECTRONIC SOUNDER POLARISED ELECTRONIC SOUNDER POLARISED SNDR1 Esento Marine 2-4 Installation, Commissioning & Operating Manual Approved Document UI-ESENMAR-01 Issue 6.0...
  • Page 12: Installation

    This product has been manufactured in conformance with the requirements of all applicable EU Council Directives Esento Marine 2-4 Installation, Commissioning & Operating Manual Approved Document UI-ESEN4MAR-01 Issue 6.0...
  • Page 13: Esd Precautions

    Knockouts should be removed with a sharp tap at the rim of the knockout using a flat 6mm broad bladed screwdriver. Use of excessive force will damage the enclosure around the knockout. Esento Marine 2-4 Installation, Commissioning & Operating Manual Approved Document UI-ESENMAR-01 Issue 6.0...
  • Page 14: Mains Connections

    Sufficient earth lead should be left to allow Live and Neutral connections to be accidentally pulled from the terminal block while leaving the earth connection intact. Esento Marine 2-4 Installation, Commissioning & Operating Manual Approved Document UI-ESEN4MAR-01 Issue 6.0...
  • Page 15: Connecting The Batteries

    There is a 30 second delay to the earth fault signal to avoid spurious faults due to noise. Esento Marine 2-4 Installation, Commissioning & Operating Manual Approved Document UI-ESENMAR-01 Issue 6.0...
  • Page 16: Setup & Programming

    Setting will change when ENTER button is pressed. Disable Test Mute Test Mode Mode Buzzer Lamps When finished, enter the next programming code or disable the controls and return DIL switch 3 to ‘OFF’. Esento Marine 2-4 Installation, Commissioning & Operating Manual Approved Document UI-ESEN4MAR-01 Issue 6.0...
  • Page 17 When finished, press and hold button 1 to store settings and exit programming mode. Then enter next programming code or return DIL switch 3 to ‘OFF’ position and disable controls. Esento Marine 2-4 Installation, Commissioning & Operating Manual Approved Document UI-ESENMAR-01 Issue 6.0...
  • Page 18 2-1-2-3. (The panel will RESOUND SILENCE RESET confirm the new access code one more time before exiting the programming mode). ENTER Disable Test Mute Test Mode Mode Buzzer Lamps Esento Marine 2-4 Installation, Commissioning & Operating Manual Approved Document UI-ESEN4MAR-01 Issue 6.0...
  • Page 19 Press button 1 to move to next option or hold button 1 for 3 seconds to exit programming mode 2-1-2-3. Note: When batteries are unmonitored the input 24v dc voltage may vary between 20v dc & 32v dc. Esento Marine 2-4 Installation, Commissioning & Operating Manual Approved Document UI-ESENMAR-01 Issue 6.0...
  • Page 20 Level 3 access mode. Enter the next programming code or disable the controls and return DIL switch 3 to ‘OFF’. Esento Marine 2-4 Installation, Commissioning & Operating Manual Approved Document UI-ESEN4MAR-01 Issue 6.0...
  • Page 21 Mute Test Mode Mode Buzzer Lamps The fire zone 1 LED will now pulse to indicate the editing of attribute 1 (fire latching) for the selected zone. Esento Marine 2-4 Installation, Commissioning & Operating Manual Approved Document UI-ESENMAR-01 Issue 6.0...
  • Page 22 Mode Mode Buzzer Lamps When finished all the zone function programming, enter the next programming code or disable the controls and return DIL switch 3 to ‘OFF’. Esento Marine 2-4 Installation, Commissioning & Operating Manual Approved Document UI-ESEN4MAR-01 Issue 6.0...
  • Page 23 Level 3 access mode. Enter the next programming code or disable the controls and return DIL switch 3 to ‘OFF’. Esento Marine 2-4 Installation, Commissioning & Operating Manual Approved Document UI-ESENMAR-01 Issue 6.0...
  • Page 24 Level 3 access mode. Enter the next programming code or disable the controls and return DIL switch 3 to ‘OFF’. Esento Marine 2-4 Installation, Commissioning & Operating Manual Approved Document UI-ESEN4MAR-01 Issue 6.0...
  • Page 25: Zone Interface Function

    With switch 1 in the ‘ON’ position, the last zone becomes; Non latching Non aux operating. Example connection ZONE2 ZONE3 ZONE4 C NC NO C NC + - + - FAULT FIRE (optional) PANEL 1 PANEL 2 Esento Marine 2-4 Installation, Commissioning & Operating Manual Approved Document UI-ESENMAR-01 Issue 6.0...
  • Page 26: Operating

    After activation by code entry, controls will automatically deactivate again after 2 minutes and the panel will return to standby mode. The test lamps and mute buzzer functions are operational without the need to activate controls. Esento Marine 2-4 Installation, Commissioning & Operating Manual Approved Document UI-ESEN4MAR-01 Issue 6.0...
  • Page 27 This button is used to confirm code entries. It can also be used for fault diagnosis (see FAULT ENTER: DIAGNOSIS section). Some buttons have other functions within the engineering facilities. These functions are described in the relevant sections. Esento Marine 2-4 Installation, Commissioning & Operating Manual Approved Document UI-ESENMAR-01 Issue 6.0...
  • Page 28: Disable Mode

    With the controls active, pressing the Disable Mode button briefly will reveal which circuits are disabled (as opposed to in test mode). This is useful if using Disable Mode and Test Mode at the same time. Esento Marine 2-4 Installation, Commissioning & Operating Manual Approved Document UI-ESEN4MAR-01 Issue 6.0...
  • Page 29: Test Mode

    With the controls active, pressing the Test Mode button briefly will reveal which circuits are in test mode (as opposed to disabled). This is useful if using Disable Mode and Test Mode at the same time. Esento Marine 2-4 Installation, Commissioning & Operating Manual Approved Document UI-ESENMAR-01 Issue 6.0...
  • Page 30: Fault Diagnosis

    Zone 1 - 4 Fault/ Zone # disabled or Disabled/Test LED in test mode (steady) Power Supply Mains failure Battery failure or Voltage fault Main PCB Fault LED (pulsing) high impedance Esento Marine 2-4 Installation, Commissioning & Operating Manual Approved Document UI-ESEN4MAR-01 Issue 6.0...
  • Page 31: Functionality During A System Fault

    Test Disable Test Mute Test Disable Test Mute Test Mode Mode Buzzer Lamps Mode Mode Buzzer Lamps Mode Mode Buzzer Lamps fig 1 fig 2 fig 3 Esento Marine 2-4 Installation, Commissioning & Operating Manual Approved Document UI-ESENMAR-01 Issue 6.0...
  • Page 32: Service & Maintenance

    The result of the weekly test and the identity or location of the manual call point used should be recorded in the system log book. Esento Marine 2-4 Installation, Commissioning & Operating Manual Approved Document UI-ESEN4MAR-01 Issue 6.0...
  • Page 33 Details of the service visit must be recorded in the log book EVERY FOUR YEARS Renew the sealed lead acid batteries and record the fact in the log book Esento Marine 2-4 Installation, Commissioning & Operating Manual Approved Document UI-ESENMAR-01 Issue 6.0...
  • Page 34 This Section To Be Used To Record ALL Weekly Tests Of The Fire Alarm System DDATE & DEVICE TESTED & COMMENTS INITIALS OF LOCATION (IF ANY) TESTER TIME OF TEST Esento Marine 2-4 Installation, Commissioning & Operating Manual Approved Document UI-ESEN4MAR-01 Issue 6.0...
  • Page 35 This Section To Be Used To Record ALL Weekly Tests Of The Fire Alarm System DDATE & DEVICE TESTED & COMMENTS INITIALS OF LOCATION (IF ANY) TESTER TIME OF TEST Esento Marine 2-4 Installation, Commissioning & Operating Manual Approved Document UI-ESEN4MAR-01 Issue 6.0...
  • Page 36 This Section To Be Used To Record ALL Weekly Tests Of The Fire Alarm System DDATE & DEVICE TESTED & COMMENTS INITIALS OF LOCATION (IF ANY) TESTER TIME OF TEST Esento Marine 2-4 Installation, Commissioning & Operating Manual Approved Document UI-ESEN4MAR-01 Issue 6.0...
  • Page 37 This Section To Be Used To Record ALL Weekly Tests Of The Fire Alarm System DDATE & DEVICE TESTED & COMMENTS INITIALS OF LOCATION (IF ANY) TESTER TIME OF TEST Esento Marine 2-4 Installation, Commissioning & Operating Manual Approved Document UI-ESEN4MAR-01 Issue 6.0...
  • Page 38 This Section To Be Used To Record ALL Weekly Tests Of The Fire Alarm System DDATE & DEVICE TESTED & COMMENTS INITIALS OF LOCATION (IF ANY) TESTER TIME OF TEST Esento Marine 2-4 Installation, Commissioning & Operating Manual Approved Document UI-ESEN4MAR-01 Issue 6.0...
  • Page 39 This Section To Be Used To Record ALL Weekly Tests Of The Fire Alarm System DDATE & DEVICE TESTED & COMMENTS INITIALS OF LOCATION (IF ANY) TESTER TIME OF TEST Esento Marine 2-4 Installation, Commissioning & Operating Manual Approved Document UI-ESEN4MAR-01 Issue 6.0...
  • Page 40 FALSE ALARMS, FAULTS & ENGINEERS VISITS Fault/Reason For Action Taken Date Work Completed Engineer’s Details Call-Out Esento Marine 2-4 Installation, Commissioning & Operating Manual Approved Document UI-ESEN4MAR-01 Issue 6.0...
  • Page 41 FALSE ALARMS, FAULTS & ENGINEERS VISITS Fault/Reason For Action Taken Date Work Completed Engineer’s Details Call-Out Esento Marine 2-4 Installation, Commissioning & Operating Manual Approved Document UI-ESEN4MAR-01 Issue 6.0...
  • Page 42 FALSE ALARMS, FAULTS & ENGINEERS VISITS Fault/Reason For Action Taken Date Work Completed Engineer’s Details Call-Out Esento Marine 2-4 Installation, Commissioning & Operating Manual Approved Document UI-ESEN4MAR-01 Issue 6.0...
  • Page 43 USER INSTRUCTIONS If an alarm condition is present YOU MUST FOLLOW YOUR NORMAL FIRE DRILL PROCEDURES. A responsible person should then:- Check the control panel to see which area or zone has caused the system to go into alarm. This will be indicated by a pulsing red LED on the front of the control panel.
  • Page 44 www.haes-tech.com...