Haes ESG-2001 Installation, Commissioning & Operating Manual

Fire control extinguishing panel
Table of Contents

Advertisement

Quick Links

ESPRIT-G FIRE CONTROL
EXTINGUISHING PANEL
INSTALLATION,
COMMISSIONING &
OPERATING MANUAL
This manual covers the installation, programming and commissioning of the Esprit
Extinguishing Fire Alarm Control Panels for One and Two Flood Zones.
www.acornfiresecurity.com
www.acornfiresecurity.com

Advertisement

Table of Contents
loading

Summary of Contents for Haes ESG-2001

  • Page 1 www.acornfiresecurity.com ESPRIT-G FIRE CONTROL EXTINGUISHING PANEL INSTALLATION, COMMISSIONING & OPERATING MANUAL This manual covers the installation, programming and commissioning of the Esprit Extinguishing Fire Alarm Control Panels for One and Two Flood Zones. www.acornfiresecurity.com...
  • Page 2: Introduction

    ESPRIT Gas Extinguishing User Manual INTRODUCTION INTRODUCTION 2797 Haes Technologies Ltd, Unit 3, Horton Industrial Park, West Drayton, Uxbridge, UB7 8JD Model Number CPR Number ESG 1002/1003/1004 2797-CPR-720738 European Standard EN54-2 : 1997 + A1 : 2006 Control and indicating equipment for fire detection and fire alarm systems for buildings.
  • Page 3 www.acornfiresecurity.com ESPRIT Gas Extinguishing User Manual INTRODUCTION List of optional functions with requirements: EN 12094-1: 2003 - Electrical automatic control and delay device. - Environmental class: A - 1 Flooding Zone - CO2 Low Pressure - CO2 High Pressure - Inert gas systems Provided options: - 4.17 Delay of extinguishing signal - 4.18 Monitor Flow of Extinguishing Agent...
  • Page 4 www.acornfiresecurity.com ESPRIT Gas Extinguishing User Manual INTRODUCTION Panels Model No. Standby Alarm Model No Model Name Current Current ESG-1002 205mA 300mA Esprit Ext Control Panel, Single Flood Zone, 3.4A PSU Esprit Ext Control Panel, Dual Flood Zone, 3.4A PSU, ESG-1003 207mA 365mA Large Cabinet...
  • Page 5: Table Of Contents

    www.acornfiresecurity.com ESPRIT Gas Extinguishing User Manual INTRODUCTION Contents INTRODUCTION ............................. 2 PRODUCT OVERVIEW .......................... 7 General Description of the Equipment ....................7 Cabinet for Single Flood Zone ......................8 Cabinet for Two Flood Zones ......................8 Circuit Boards ..........................9 Circuit Description/Function ......................
  • Page 6 www.acornfiresecurity.com ESPRIT Gas Extinguishing User Manual INTRODUCTION Fault Condition ..........................39 CONFIGURING THE SYSTEM......................41 Accessing the Menu Structure......................41 Learn System ............................ 42 Set Common Output for HOLD & ABORT ..................44 User Menu ............................46 User Menu: AUTO/MANUAL MODE Menu ................... 46 User Menu: DISABLE ........................
  • Page 7: Product Overview

    www.acornfiresecurity.com ESPRIT Gas Extinguishing User Manual PRODUCT OVERVIEW PRODUCT OVERVIEW General Description of the Equipment The ESPRiT-G extinguishing gas panel acts as both a conventional fire alarm panel and an automatic extinguisher control panel and was designed from the ground up to be intuitive and flexible for the engineer.
  • Page 8: Cabinet For Single Flood Zone

    www.acornfiresecurity.com ESPRIT Gas Extinguishing User Manual PRODUCT OVERVIEW Cabinet for Single Flood Zone Cabinet for Two Flood Zones Approved Document Ref: UI-ESG-01 Issue 2.0 www.acornfiresecurity.com...
  • Page 9: Circuit Boards

    www.acornfiresecurity.com ESPRIT Gas Extinguishing User Manual PRODUCT OVERVIEW Circuit Boards 2827-206 DISPLAY CARD & 2972-206 EXTENSION LEDs CARD (2nd Flood Zone) Approved Document Ref: UI-ESG-01 Issue 2.0 www.acornfiresecurity.com...
  • Page 10 www.acornfiresecurity.com ESPRIT Gas Extinguishing User Manual PRODUCT OVERVIEW 2879-206 PSU CARD & 2883-206 GAS CARD Approved Document Ref: UI-ESG-01 Issue 2.0 www.acornfiresecurity.com...
  • Page 11: Circuit Description/Function

    www.acornfiresecurity.com ESPRIT Gas Extinguishing User Manual PRODUCT OVERVIEW Circuit Description/Function TPC2827-206 DISPLAY CARD IP1/IP2/0V Monitored inputs for Activate Controls (IP1/0V) and Select Mode (IP2/0V) key switches. IP3/IP4 Not used. TPC2972-206 EXTENSION LEDs CARD (2 Flood Zone) 28V/0V 28V input. 0V/IP1 Monitored input from Flood Zone 2 Select Mode key switch.
  • Page 12 www.acornfiresecurity.com ESPRIT Gas Extinguishing User Manual PRODUCT OVERVIEW BATTERY (+ -) Connections for two VRLA batteries (up to 18Ahr, depending on cabinet size) charging output (temperature compensated). 27.4VDC output at 20°C, Max. 700mA. TEMP SENS (* *) Connections for battery temperature sensor. TPC2883-206 Gas Card ZONE 1 (+ -)/ZONE 2 (+ -)/ZONE 3 (+ -) Conventional fire zone circuits, coincidence circuit inputs.
  • Page 13: Technical Specification

    www.acornfiresecurity.com ESPRIT Gas Extinguishing User Manual Technical Specification Technical Specification General Specification Enclosure Steel IP30. Epoxy powder coated Interpon Radon, silver grey Cabling Fire resistant screened cable, minimum size 1mm . Max cable length 1Km (20 Ohm). Fire Burn, FP200 or equivalent (max capacitance 1uF, max inductance 1 millihenry).
  • Page 14 www.acornfiresecurity.com ESPRIT Gas Extinguishing User Manual Technical Specification Min/max battery size and 2 x 3.2 Ah 12volt VRLA Small cabinet type (minimum) 2 x 7Ah 12volt VRLA (1 Flood zone) 2 x 18.0Ah 12volt VRLA. (1 or 2 Large cabinet Flood zone) Use Yuasa NP range batteries Battery charging voltage...
  • Page 15 www.acornfiresecurity.com ESPRIT Gas Extinguishing User Manual Technical Specification Electrical Specification Inputs & Outputs – TPC2879-206 PSU PCB for Single and Dual Flood Zone Panels Terminal capacity 0.5mm to 2.5mm solid or stranded wire. PSU Input +/- to PCB 29.5VDC supply input. Diode Max input current 5 amps.
  • Page 16 www.acornfiresecurity.com ESPRIT Gas Extinguishing User Manual Technical Specification EXT OP +/- Extinguishant Release Output. 21- 30VDC: 2A continuous rated for 28VDC polarity reversal monitored solenoids; output to Solenoids or Metron 3A at 450mS available for Metron actuators. actuators 1N4002 diode EOL, Circuit parameters learnt during commissioning.
  • Page 17: Installation Consideration

    www.acornfiresecurity.com ESPRIT Gas Extinguishing User Manual INSTALLATION INSTALLATION Safety Important notice: Please read this manual before handling the equipment and observe all advice given within it. Important Notes: The product must be installed, commissioned and maintained for operation in accordance with the instructions and the applicable wiring codes of practice and national standard regulations for fire systems appropriate to the country and location of the installation.
  • Page 18: Esd Precaution

    www.acornfiresecurity.com ESPRIT Gas Extinguishing User Manual INSTALLATION ESD Precaution This particularly applies to the precautions necessary to avoid Electro-Static Discharge. Attention – Observe precaution for handling electro-static sensitive devices. This equipment is constructed with static sensitive components. Wear an anti-static earth strap connected to panel enclosure earth point.
  • Page 19: Mains Connections

    www.acornfiresecurity.com ESPRIT Gas Extinguishing User Manual INSTALLATION Mains Connections Note: All connection must be carried out in accordance to local requirements and regulations. Connecting the Batteries Note: In the event of mains failure, the battery charger circuit will protect the batteries from full discharge by disconnecting them when they reach below 19v.
  • Page 20: Battery Charging Voltage Checks

    www.acornfiresecurity.com ESPRIT Gas Extinguishing User Manual INSTALLATION Battery Charging Voltage Checks ° The battery charging voltage is factory calibrated to 27.3VDC +/- 0.2V at 20 C. This should not normally require adjustment. Where battery problems are experienced, the following information should be considered.
  • Page 21: Detection Zone Inputs

    www.acornfiresecurity.com ESPRIT Gas Extinguishing User Manual INSTALLATION BATTERY VOLTS: nn.nn CHARGE: nn.nn Current: n.nn DAC OUTPUT: nnn.nn VREF INT: nnnn CALIBRATION: n.nnnnnn • Place Multimeter probes onto battery input terminals and observe the Battery Volts reading • Using Up/Down arrow keys; adjust the calibration until the BATTERY VOLTS figure, shown on the panel LCD screen, matches the Battery Voltage as measured on the Multimeter •...
  • Page 22: Sounders / Monitored Output Circuits

    www.acornfiresecurity.com ESPRIT Gas Extinguishing User Manual INSTALLATION Intrinsic Safe Connections The Zone Circuit can be configured for use with Intrinsic Safety detectors and barriers: please see the programming section. HAZARDOUS AREA IS Detector IS Detector IS Call Point Isolation Barrier 11 + 1 12 - SAFE AREA...
  • Page 23: Relay Outputs

    www.acornfiresecurity.com ESPRIT Gas Extinguishing User Manual INSTALLATION Relay Outputs The panel is equipped with six relay outputs. Each output is unsupervised with volt-free changeover contacts rated at 30VAC/DC, 1A, resistive. The Fault Relays and Fire Relays are fixed to indicate their respective conditions. The Fault Relay is normally activated.
  • Page 24: Inputs - Class Change And Pulse

    www.acornfiresecurity.com ESPRIT Gas Extinguishing User Manual INSTALLATION Inputs - Class Change and Pulse Class Change Switch (–ve) inputs, which cause the common sounder outputs to operate. Note: Stage sounders will not be affected unless programmed to do so (see program details). Pulse Switch (–ve) inputs which cause the common sounder and detection zone stage sounder’s outputs to pulse.
  • Page 25: Monitored Input Wiring

    www.acornfiresecurity.com ESPRIT Gas Extinguishing User Manual INSTALLATION Monitored Input Wiring Six monitored input connections are available on the panel Gas Card for each Flood Zone: Manual Release, Flow Switch, Pressure switch, Auto\manual only Mode, Hold and Abort. Figure Above: Typical Monitored Input Wiring A 6k8 end-of-line resistor must be connected across the terminals of last device on each circuit to allow the wiring to be line monitored for open and short circuit faults.
  • Page 26: Solenoid Actuators

    www.acornfiresecurity.com ESPRIT Gas Extinguishing User Manual INSTALLATION Solenoid Actuators A Back-EMF diode must be fitted across the solenoid coil. Observe polarity – see diagram below. Coil resistance 25Ω-200Ω. Maximum line impedance 1.5Ω -5.0Ω depending on coil impedance – see calculation below. Two solenoids can be connected in parallel.
  • Page 27: Remote Status Unit (Rsu) Wiring

    www.acornfiresecurity.com ESPRIT Gas Extinguishing User Manual INSTALLATION Remote Status Unit (RSU) Wiring The RSU and mini RSU require a 4-wire connection (2 wires for 28Vpower, 2 wires for RS485 data) from the control panel. Each RSU has a PCB-mounted DIL switch and must be allocated a unique address between 1 and 16. When Two Flood zones are in use, it is possible to assign RSUs to either Flood Zone.
  • Page 28: Operating Instructions

    www.acornfiresecurity.com ESPRIT Gas Extinguishing User Manual OPERATING INSTRUCTIONS OPERATING INSTRUCTIONS Panel Control and Indicators Control Panel The Control Panel contains: • LCD Display Screen • Control Keypads • Manual Extinguisher Release • Status LED Indicators • Activate Controls Key Operated Switch •...
  • Page 29 www.acornfiresecurity.com ESPRIT Gas Extinguishing User Manual OPERATING INSTRUCTIONS Keypads Resound Use to resound the alarms after they have been silenced. Can also be Alarms used to invoke full evacuation. Silence Alarms Use to silence the sounders during an alarm condition. Reset System Resets the panel back to standby mode.
  • Page 30 www.acornfiresecurity.com ESPRIT Gas Extinguishing User Manual OPERATING INSTRUCTIONS Status LED Indicators LED Name LED ON LED PULSING Zones in Fire 1 - 3 Indicates alarm condition in zone. Zone Fault/Test/Disabled/ 1 - Indicates a zone circuit is Indicates a fault in the zone disabled or in test mode.
  • Page 31 www.acornfiresecurity.com ESPRIT Gas Extinguishing User Manual OPERATING INSTRUCTIONS LED Name LED ON LED PULSING Indicates that the imminent Indicates a fault in the Abort Aborted release of extinguishant has Circuit been aborted Flood zone is disabled or in test A Fault exists which may Flood Zone Fault mode prevent the release of...
  • Page 32: User Controls

    www.acornfiresecurity.com ESPRIT Gas Extinguishing User Manual OPERATING INSTRUCTIONS User Controls Four levels of control, with programmable code entry, are available on the panel: • General User (Access Level 1) • Authorised User (Access Level 2) • Engineer (Access Level 3) (CONFIG Mode) •...
  • Page 33: Authorized User Controls

    www.acornfiresecurity.com ESPRIT Gas Extinguishing User Manual OPERATING INSTRUCTIONS OTHER A00 F00 D00 O01 1: MANUAL MODE AREA 1 ON RSU nn Note: The system may have many inputs for selecting Manual Only Mode, from RSUs or mini RSUs connected to the system. Any one of these set in the manual condition will override the main panel setting.
  • Page 34: Engineer Controls

    www.acornfiresecurity.com ESPRIT Gas Extinguishing User Manual OPERATING INSTRUCTIONS Engineer Controls (Access Level 3) The Engineer (Access level 3) controls can be accessed by: • From the Authorised User (Access level 2) Main Menu, use Left/Right arrow keys to move cursor to: CONFIG menu or CONTROL menu >...
  • Page 35 www.acornfiresecurity.com ESPRIT Gas Extinguishing User Manual OPERATING INSTRUCTIONS • The ALARM COUNT sub-menu will open, and the following information will be available: ALARM COUNT: nnnn (number (n) of alarm events that have occurred) LAST ALARM AT: dd-MMM-yy hh:mm:ss (date and time when the last event happened) HOLD DOWN SELECT TO RESET: •...
  • Page 36: Panel Alarm Conditions

    www.acornfiresecurity.com ESPRIT Gas Extinguishing User Manual OPERATING INSTRUCTIONS Panel Alarm Conditions Fire Alarm Condition Depending on the panel type (single or double Flood Zone) and the Gas Cards installed, the panel can have one or two Flood Zones. Each Flood Zone can have 1 – 3 Detection Zones. The panel will enter a fire alarm condition if: •...
  • Page 37 www.acornfiresecurity.com ESPRIT Gas Extinguishing User Manual OPERATING INSTRUCTIONS Release (Stage 2) When the timer reaches ‘0’ the extinguishant is released: • Release Imminent LED is off • Release Imminent sounder (1st Stage Sounder) is silenced • Flow switch is triggered, starting the release of extinguishant (Flow switch would need a trigger- 470Ω).
  • Page 38 www.acornfiresecurity.com ESPRIT Gas Extinguishing User Manual OPERATING INSTRUCTIONS Panel Programmed Condition - (Flow SW Y/N to N - Auto) If, during configuration of the system’s Gas Card options, the Flow Switch is set to N - Auto (for the panel programmed condition), the extinguishant release status is indicated as follows: Release Imminent (Stage 1) When the release/activated condition is established: •...
  • Page 39: Hold Condition

    www.acornfiresecurity.com ESPRIT Gas Extinguishing User Manual OPERATING INSTRUCTIONS Extract (Stage 2) When the timer reaches ‘0’ flooding is complete and (if programmed), the panel will automatically activate the output to control the extract fan: • The display shows EXTRACT, and a countdown timer with the time elapsed since the start of the zone extraction began •...
  • Page 40 www.acornfiresecurity.com ESPRIT Gas Extinguishing User Manual OPERATING INSTRUCTIONS Functionality During a System Fault A system fault is indicated when a processor controlling a function in the panel has a watchdog time out, or processor failure. In the event of a system fault, the board affected may not be functional. The following indications may be observed: •...
  • Page 41: Configuring The System

    www.acornfiresecurity.com ESPRIT Gas Extinguishing User Manual CONFIGURING THE PANEL CONFIGURING THE PANEL When the system is installed and is ready to be commissioned, configuring the system consists of: • Use the CONFIG PANEL menu LEARN option - On initial commissioning; or following removal or addition of external device(s) (sounder, call point, detector, etc.), set the system to automatically learn what internal cards, external devices and RSUs are connected.
  • Page 42: Learn System

    www.acornfiresecurity.com ESPRIT Gas Extinguishing User Manual CONFIGURING THE PANEL The Box surrounding the menu icon is the cursor, this is used to navigate through the menu options by using the Left/Right arrow keys to select required menu option and then press ✓ button. The Left/Right and Up/Down arrow keys can then be used to access further sub-menus and options, within the main menus, and then press ✓...
  • Page 43 www.acornfiresecurity.com ESPRIT Gas Extinguishing User Manual CONFIGURING THE PANEL • On completion of the learning routine, the LEARN PANEL sub-menu will display all the internal cards found connected, or not, indicated by YES or NO: -INTERNAL CARDS- 1: PSU CARD: YES/NO 2: GAS ONE: YES/NO 3: GAS TWO: YES/NO 4: AREA Two Fascia: YES/NO...
  • Page 44: Set Common Output For Hold & Abort

    www.acornfiresecurity.com ESPRIT Gas Extinguishing User Manual CONFIGURING THE PANEL Set Common Output for HOLD & ABORT It is possible to set any of the outputs for use as a common output indication, to show activation of HOLD and ABORT functions for both Single and Dual flood zone Panels. A Sounder or Relay output can be used to provide this common indication.
  • Page 45 www.acornfiresecurity.com ESPRIT Gas Extinguishing User Manual CONFIGURING THE PANEL • When the required changes are completed, press return button to return to DEVICES Menu. A short sequence of buzzer beeps will indicate that changes have been stored in memory. • button and the ✓...
  • Page 46: User Menu

    www.acornfiresecurity.com ESPRIT Gas Extinguishing User Manual CONFIGURING THE PANEL User Menu Accessible from the Main Menu (Access level 2), the User menu and its subsequent sub-menus, are used to set-up the panel ready for configuration. The sub-menus available are: • User AUTO/MANUAL MODE DISABLE...
  • Page 47: User Menu: Disable

    www.acornfiresecurity.com ESPRIT Gas Extinguishing User Manual CONFIGURING THE PANEL • key and the ✓ button, as required. To go back to the main logo screen, press the return On selection of MANUAL mode, the Manual Only LED will be illuminated and the display shows: OTHER A00 F00 D00 O01 1: MANUAL MODE ACTIVE...
  • Page 48: User Menu: Time & Date

    www.acornfiresecurity.com ESPRIT Gas Extinguishing User Manual CONFIGURING THE PANEL 26: EXT-OP: ENABLED / DISABLED 27: MAN RELEASE INPUT: ENABLED / DISABLED 28: FLOW SWITCH INPUT: ENABLED / DISABLED 29: LOW PRESSURE INPUT: ENABLED / DISABLED 30: HOLD INPUT: ENABLED / DISABLED 31: ABORT INPUT: ENABLED / DISABLED 32: AUTO MAN INPUT: ENABLED / DISABLED 33: LOCAL FIRE Relay: ENABLED / DISABLED...
  • Page 49: User Menu: Lamp Test

    www.acornfiresecurity.com ESPRIT Gas Extinguishing User Manual CONFIGURING THE PANEL • Under the Set DayLight Savings sub-menu, the following options are displayed: Set DayLight Savings Menu Starts: LAST Sunday Ends: LAST Sunday Auto Update DayLight Savings: YES/NO DST: ACTIVE/INACTIVE • To change the Set DayLight Savings Menu sub-menu options, to match local start and end of DST: Use Left/Right arrow keys to move between the various fields (indicated by underline curser).
  • Page 50: User Menu: Buzzer

    www.acornfiresecurity.com ESPRIT Gas Extinguishing User Manual CONFIGURING THE PANEL User Menu: BUZZER To set the volume for the panel internal buzzer, operate the BUZZER menu: • On the Main Menu, use Left/Right arrow keys to move cursor box to User menu •...
  • Page 51: User Menu/Sub-Menu Breakdown

    www.acornfiresecurity.com ESPRIT Gas Extinguishing User Manual CONFIGURING THE PANEL User Menu Breakdown Approved Document Ref: UI-ESG-01 Issue 2.0 www.acornfiresecurity.com...
  • Page 52 www.acornfiresecurity.com ESPRIT Gas Extinguishing User Manual CONFIGURING THE PANEL Approved Document Ref: UI-ESG-01 Issue 2.0 www.acornfiresecurity.com...
  • Page 53: Config Menu

    www.acornfiresecurity.com ESPRIT Gas Extinguishing User Manual CONFIGURING THE PANEL CONFIG Menu Accessible from the Main Menu (Access level 2); the CONFIG Menu (Access level 3), and its subsequent sub-menus, are used to configure the panel and its attached devices. The sub-menus available are: •...
  • Page 54: Config Menu: Panel

    www.acornfiresecurity.com ESPRIT Gas Extinguishing User Manual CONFIGURING THE PANEL CONFIG Menu: PANEL Under the PANEL sub-menu, the following sub-menus are available to configure the panel controls and outputs: • LEARN • OPTIONS • SET DEFAULT PARAMETERS • SET PASSWORDS CONFIG PANEL Menu: LEARN To set the system to learn what internal cards, external devices and RSUs are connected, access the LEARN PANEL sub-menu: •...
  • Page 55 www.acornfiresecurity.com ESPRIT Gas Extinguishing User Manual CONFIGURING THE PANEL Press return key again P-BUS: The LEARN PANEL sub-menu will display a list containing all 16 RSUs and show if they are connected or not, using the P-BUS, indicated by the Gas area the RSU is connected to, or NOT PRESENT: -P-BUS- 1: FIRST RSU: GAS AREA ONE/GAS AREA TWO/NOT PRESENT...
  • Page 56 www.acornfiresecurity.com ESPRIT Gas Extinguishing User Manual CONFIGURING THE PANEL Note: When a circuit goes into Fire Alarm, option 4 sets a time delay of up to 30 minutes before the sounders and extinguishant release are activated. This is to protect against possible false alarms.
  • Page 57: Config Menu: Gas Card

    www.acornfiresecurity.com ESPRIT Gas Extinguishing User Manual CONFIGURING THE PANEL CONFIG Menu: GAS CARD To configure the Gas Card: • On the CONFIG Menu, highlight PANEL option and then press ✓ key to gain access to it. • Highlight GAS CARD option and then press ✓ key in order to gain access to it. •...
  • Page 58: Config Menu: Devices

    www.acornfiresecurity.com ESPRIT Gas Extinguishing User Manual CONFIGURING THE PANEL CONFIG Menu: DEVICES Under the Devices sub-menu, the following sub-menus are available to configure the external devices and outputs: • ZONES • SOUNDERS • Relay CONFIG DEVICES Menu: Zones To configure the options for the Flood Zones/Detection Zones: •...
  • Page 59 www.acornfiresecurity.com ESPRIT Gas Extinguishing User Manual CONFIGURING THE PANEL • The information available under SOUNDERS menu will be presented as follows: SOUNDERS <PSU SNDR ONE/PSU SNDR TWO/GAS AREA ONE STAGE 1/GAS AREA ONE STAGE 2/GAS AREA TWO STAGE 1/GAS AREA TWO STAGE 2>...
  • Page 60 www.acornfiresecurity.com ESPRIT Gas Extinguishing User Manual CONFIGURING THE PANEL CONFIG DEVICES Menu: RELAYS To configure the Relay outputs: • On the CONFIG Menu, highlight Devices option and then press ✓ key to gain access to it. • On the CONFIG Devices sub-menu, highlight the Relay option and press the ✓ key again. •...
  • Page 61: Config Menu: P-Bus

    www.acornfiresecurity.com ESPRIT Gas Extinguishing User Manual CONFIGURING THE PANEL CONFIG Menu: P-BUS To configure the P-BUS, access the P-BUS menu. • From the CONFIG sub-menu, highlight P-BUS option and then press the ✓ key in order to gain access to it. •...
  • Page 62: Config Menu/Sub-Menu Breakdown

    www.acornfiresecurity.com ESPRIT Gas Extinguishing User Manual CONFIGURING THE PANEL CONFIG Menu Breakdown Approved Document Ref: UI-ESG-01 Issue 2.0 www.acornfiresecurity.com...
  • Page 63 www.acornfiresecurity.com ESPRIT Gas Extinguishing User Manual CONFIGURING THE PANEL Approved Document Ref: UI-ESG-01 Issue 2.0 www.acornfiresecurity.com...
  • Page 64 www.acornfiresecurity.com ESPRIT Gas Extinguishing User Manual CONFIGURING THE PANEL Approved Document Ref: UI-ESG-01 Issue 2.0 www.acornfiresecurity.com...
  • Page 65 www.acornfiresecurity.com ESPRIT Gas Extinguishing User Manual CONFIGURING THE PANEL Approved Document Ref: UI-ESG-01 Issue 2.0 www.acornfiresecurity.com...
  • Page 66 www.acornfiresecurity.com ESPRIT Gas Extinguishing User Manual CONFIGURING THE PANEL Approved Document Ref: UI-ESG-01 Issue 2.0 www.acornfiresecurity.com...
  • Page 67 www.acornfiresecurity.com ESPRIT Gas Extinguishing User Manual CONFIGURING THE PANEL Approved Document Ref: UI-ESG-01 Issue 2.0 www.acornfiresecurity.com...
  • Page 68: Control Menu

    www.acornfiresecurity.com ESPRIT Gas Extinguishing User Manual CONFIGURING THE PANEL CONTROL Menu From the Main Menu, the CONTROL menu (Access level 3) option, and its sub-menus, is used to configure the extinguishant’s release and extraction: • CONTROL EXTRACT FLOODING DELAYS To access the CONTROL menu: •...
  • Page 69: Control Menu: Flooding

    www.acornfiresecurity.com ESPRIT Gas Extinguishing User Manual CONFIGURING THE PANEL Control Menu: FLOODING To configure the FLOODING controls, access the FLOODING menu. • From the CONTROL Menu, highlight FLOODING option and then press the ✓ key in order to gain access to it, the following will be displayed: Enter Level 3 Access Code •...
  • Page 70: Control Menu/Sub-Menu Breakdown

    www.acornfiresecurity.com ESPRIT Gas Extinguishing User Manual CONFIGURING THE PANEL CONTROL Menu Breakdown Approved Document Ref: UI-ESG-01 Issue 2.0 www.acornfiresecurity.com...
  • Page 71: Report Menu

    www.acornfiresecurity.com ESPRIT Gas Extinguishing User Manual CONFIGURING THE PANEL Report Menu From the Report Menu, accessible from the Main Menu, the following sub-menus are available: • Report ALARM FAULT DISABLE OTHER HISTORY Versions COUNTER Gas Card PSU Card BATTERY To access the Report Menu: •...
  • Page 72: Report Menu: Fault

    www.acornfiresecurity.com ESPRIT Gas Extinguishing User Manual CONFIGURING THE PANEL • The number (n) of Alarm events will be displayed in the following manner: ALARM A nn F 00 D 00 O 00 List of detected alarms ALARM FFRE : NORMAL/ACTIVE and/or FARE : NORMAL/ACTIVE List of detected alarms (Displayed if Sounder One FARE and/or Sounder Two FFRE are selected to YES, under CONFIG : PANEL : OPTIONS, during configuration)
  • Page 73: Report Menu: Disable

    www.acornfiresecurity.com ESPRIT Gas Extinguishing User Manual CONFIGURING THE PANEL Report Menu: DISABLE From the DISABLE sub-menu; the number of system disablements is displayed. To get DISABLE events information: • Turn Activate Controls key clockwise to On • Use the keypad to enter Authorised User (Access level 2) code 1111: Press ✓...
  • Page 74: Report Menu: Other

    www.acornfiresecurity.com ESPRIT Gas Extinguishing User Manual CONFIGURING THE PANEL Report Menu: OTHER From the OTHER sub-menu; the number of OTHER system events (any event not covered by ALARM, FAULT, DISABLE, etc.) is displayed. To get OTHER events information: • On the Main Menu, use Left/Right arrow keys to move cursor to Report menu icon and press ✓...
  • Page 75: Report Menu: History

    www.acornfiresecurity.com ESPRIT Gas Extinguishing User Manual CONFIGURING THE PANEL Report Menu: HISTORY To get event history information: • On the Main Menu, use Left/Right arrow keys to move cursor to Report menu icon and press ✓ key to select. • From the Report Menu, use Left/Right arrow keys to move curser to select HISTORY sub- menu.
  • Page 76: Report Menu: Versions

    www.acornfiresecurity.com ESPRIT Gas Extinguishing User Manual CONFIGURING THE PANEL Report Menu: Versions To access the software Versions information: • On the Main Menu, use Left/Right arrow keys to move cursor box to Report menu. • Press ✓ key to select the Report menu. •...
  • Page 77: Report Menu: Gas Card

    www.acornfiresecurity.com ESPRIT Gas Extinguishing User Manual CONFIGURING THE PANEL • Press return key to return to Report Menu. • Press return key again to return to the Main Menu. Report Menu: Gas Card To get status information on the system’s Gas Card(s): •...
  • Page 78 www.acornfiresecurity.com ESPRIT Gas Extinguishing User Manual CONFIGURING THE PANEL • key or ✓ key to return to the Report Menu. A short Next, press return acknowledgement sound will be present. Approved Document Ref: UI-ESG-01 Issue 2.0 www.acornfiresecurity.com...
  • Page 79: Report Menu/Sub-Menu Breakdown

    www.acornfiresecurity.com ESPRIT Gas Extinguishing User Manual CONFIGURING THE PANEL Report Menu Breakdown Approved Document Ref: UI-ESG-01 Issue 2.0 www.acornfiresecurity.com...
  • Page 80 www.acornfiresecurity.com ESPRIT Gas Extinguishing User Manual CONFIGURING THE PANEL Approved Document Ref: UI-ESG-01 Issue 2.0 www.acornfiresecurity.com...
  • Page 81 www.acornfiresecurity.com ESPRIT Gas Extinguishing User Manual CONFIGURING THE PANEL Approved Document Ref: UI-ESG-01 Issue 2.0 www.acornfiresecurity.com...
  • Page 82 www.acornfiresecurity.com ESPRIT Gas Extinguishing User Manual CONFIGURING THE PANEL Approved Document Ref: UI-ESG-01 Issue 2.0 www.acornfiresecurity.com...
  • Page 83: Eng Menu

    www.acornfiresecurity.com ESPRIT Gas Extinguishing User Manual CONFIGURING THE PANEL ENG Menu From the ENG menu option on the Main Menu, the following sub-menus can be accessed: • Test ▪ ON/OFF ▪ SETTINGS MISC The ENG menu is used to: • Test the system and set which Gas Area zones are to be included/excluded from the test •...
  • Page 84 www.acornfiresecurity.com ESPRIT Gas Extinguishing User Manual CONFIGURING THE PANEL Note: OFF will de-activate Test Mode function, so that any zones set for this mode will still activate Fire Alarms in the standard way • When selection is made, press return key to return to Test MODE sub-menu screen.
  • Page 85: Eng Menu: Misc

    www.acornfiresecurity.com ESPRIT Gas Extinguishing User Manual CONFIGURING THE PANEL ENG Menu: MISC The MISC sub-menu is used to remove all disablements currently set in the system: • On the Main Menu, use Left/Right arrow keys to move cursor to ENG menu icon and press ✓ key to select.
  • Page 86: Eng Menu/Sub-Menu Breakdown

    www.acornfiresecurity.com ESPRIT Gas Extinguishing User Manual CONFIGURING THE PANEL ENG Menu Breakdown Approved Document Ref: UI-ESG-01 Issue 2.0 www.acornfiresecurity.com...
  • Page 87: Service & Maintenance

    www.acornfiresecurity.com ESPRIT Gas Extinguishing User Manual SERVICE & MAINTENANCE SERVICE & MAINTENANCE Periodic system maintenance should be carried out on the system as prescribed in the local design, maintenance and installation regulations. The fire alarm panel’s standby batteries should be checked for: •...
  • Page 88 www.acornfiresecurity.com...