www.acornfiresecurity.com Item Specification Details HS-5100 HS-5200 HS-5400 Enclosure Steel IP30 Steel IP30 Steel IP30 Dimensions H x W x 345 x 345 x 85 345 x 430 x 120 475 x 450 x 120 D mm (/M) 345 x 430 x 120 (/L) 475 x 450 x 120 (/D) 475 x 450 x 190 (/L) 475 x 450 x 120...
www.acornfiresecurity.com 1 Introduction Standards Advanced Electronics Ltd declare that the products identified below conform to the essential requirements specified in the Construction Products Directive 89/106/EEC: 0786-CPD-20952 EN54-2: 1997 +A1:2006 Control and indicating equipment for fire detection and fire alarm systems for buildings Provided options: Outputs to Fire Alarm Devices Output to Fire Routing Equipment...
www.acornfiresecurity.com Cautions and Warnings BEFORE INSTALLATION – Refer To the Ratings shown on the label inside the product and to the ‘Specifications Chart’ in this document. STOP Please read this manual carefully. If you are unclear on any point DO NOT proceed.
www.acornfiresecurity.com All panel models are available in a range of enclosure sizes and with a range of alternative optional features. Install the panel, detection loops, sounder circuits, etc. in accordance with the instructions in Section and then program the operation in accordance with the instructions detailed in Section EN54 Functions This Fire Alarm Control Panel is compliant with the requirements of EN54-2 (1997)
Page 9
www.acornfiresecurity.com Page 9 of 72 www.acornfiresecurity.com...
www.acornfiresecurity.com EN54 Optional Features with Requirements In addition to the mandatory requirements of EN54 Part 2, the Control and Indicating Equipment (C.I.E) supports the following optional features with requirements: - Outputs to Fire Alarm Devices. The C.I.E has provision for connection to Fire Alarm Devices. It is possible to Silence and Resound the alarms at Level 2.
www.acornfiresecurity.com Disablement of Points. The C.I.E has provision for enabling and disabling signals from points. Refer to the Section 9.5 User Manual for further information. Test Condition. The C.I.E has provision for testing the installation on a per zone basis. Refer to the Section 10 User Manual for further information.
www.acornfiresecurity.com 2 Installation Identification of Parts The following diagrams show the major parts of the panels. 2.1.1 HS-5100 /S Enclosure comprises: Back Box Door Back box Base Card with 1x Loop AC Input Driver mounted onto a Chassis Plate Door with Display Card Display Cable mounted onto a fascia...
www.acornfiresecurity.com 2.1.2 HS-5200 /M Enclosure comprises: Back Box Base Card with 2x Loop Door Back box Display Drivers mounted onto a AC Input Chassis Plate Door with Display Card mounted onto a fascia Display Cable plate. Key-Lock. WARNING: HI GH VOLTAGE INSIDE Option for eight key- DO NOT REMOVE COVER No Ser viceable Parts Inside...
www.acornfiresecurity.com 2.1.3 HS-5400 /L, /D Enclosures comprises: Back Box Base Card with 1-4 Door Back box Display Loop Drivers mounted AC Input onto a Chassis Plate Door with Display Card mounted onto a fascia plate. Key-Lock. Display Cable Option for eight key- WARNING: HIGH VOLTAGE INSID DO NOT REMOVE COVER...
www.acornfiresecurity.com 2.2 Installing the Enclosure The panel weight is heavy when the batteries are installed. Use the appropriate fixing hardware to secure the panel to the wall. Observe recommended lifting practices to guard against spinal injury. See table below for maximum weights. Enclosure Weight Maximum Battery...
www.acornfiresecurity.com 2.2.5 Recommended Cable Routing Arrangement It is recommended that the typical routing arrangement AC INPUT shown in the diagram opposite be employed. LOOPS AUX, PBUS & SW I/P RELAYS SOUNDERS Segregate the low AC Input voltage wiring (Loop Circuit, Sounder Circuits and AUX Supply) from the AC Mains Wiring.
www.acornfiresecurity.com 2.3 Loop Driver Installation The HS-5100, HS-5100V and HS-5100N panels are factory fitted with one loop driver. The HS-5200, HS-5200V and HS-5200N panels can be fitted with up to two loop drivers – factory fitted with at least one loop driver. The HS-5400, HS-5400V and HS-5400N panels can be fitted with up to four loop drivers –...
www.acornfiresecurity.com 2.3.2 Removing a Loop Driver Card To remove a loop driver, remove all power and follow the procedure above but: Take a firm hold of top of the loop driver card. Gradually and carefully pull the loop driver vertically away from the base card and guide it out of the slots in the card guides.
www.acornfiresecurity.com 2.4.2 2-Way Relay Card (Plug-In) The HSP-507 Relay 2-Way Relay card is fitted to the base card using 2x plastic pillars. Refer to the diagram opposite. All signals and power required for operation of the card are provided WARNING: HIGH VOLTAGE INSIDE on the plug-in DO NOT REMOVE COVER...
www.acornfiresecurity.com 2.4.4 Peripheral Module Chassis Mounting A Peripheral Module can be installed onto the chassis plate in the medium, large and deep enclosures. The peripheral card is fitted to the chassis using 4x M3 screws. All cards require connections to a 24V DC supply (AUX 24V) and to the PBUS communications. Refer to wiring section for further information.
www.acornfiresecurity.com 2.4.5 VdS Interface Module Chassis Mounting An HSP-504 VdS Interface Module can be installed onto the chassis plate in the medium, large and deep enclosures. Outputs to Routing Equipment – Clauses 7.9 and 8.9. The Routing Interface Card provides monitored outputs for connection to Fire Routing Equipment (Item E) in accordance with EN54-2.
www.acornfiresecurity.com Wiring Installation All electrical wiring installation work should be carried out in accordance with the code of practice or applicable national standards appropriate to the country of installation. To maintain electrical integrity of the SELV wiring on the input, output, loop and communications lines all SELV wiring should be segregated from the LV mains wiring and be wired using cable with insulation suitable for the application.
www.acornfiresecurity.com 2.5.2 Battery Installation The panel requires two 12V Base Card Terminations batteries for standby operation. The battery leads are connected onto the base card via a two-part plug and socket, as shown in the diagram opposite. Refer to the Specifications for minimum and maximum battery WARNING: HIGH VOLTAGE INSIDE...
www.acornfiresecurity.com 2.5.2.2 Medium Enclosure The diagrams opposite show the recommended location and orientation for 7Ah – 12AH batteries within the panel. WARNING: HI GH VOLTAGE INSIDE DO NOT REMOVE COVER No Serviceable Parts Inside 2.5.2.3 Large Enclosure The diagrams opposite show the recommended location and orientation for 7Ah –...
www.acornfiresecurity.com 2.5.2.4 Deep Enclosure The diagrams opposite show the recommended location and orientation for 7Ah – 38AH/45AH batteries within the panel. WARNING: HIGH VOLTAGE INSID DO NOT REMOVE COVER No Serviceable Parts Inside Page 26 of 72 www.acornfiresecurity.com...
www.acornfiresecurity.com 2.5.3 Detector Loop Installation Maximum of 32 Sensors / Call Points in a Zone (between Isolators). The Detection Loop Circuit should be installed as a continuous Clause 6.2.5 Not more than 128 V d S loop with isolator modules such that a short circuit condition devices per loop does not remove more than one zone or 32 input devices.
www.acornfiresecurity.com 2.5.4 Sounder Circuits The HS-5100 & HS5200 are equipped with two supervised sounder circuits. These are denoted as Circuits A and B. The HS-5400 is equipped with four supervised sounder circuits. These are denoted as Circuits A, B, C and D. Each Sounder output is rated at a maximum of 1 Ampere.
www.acornfiresecurity.com 2.5.5 Network Interface The network permits the connection of other panels, remote terminals and other devices to complete a distributed system. Either an HSP-503 (STD) standard network interface card or an HSP-509 (FT) fault tolerant network interface card must be installed in the panel.
www.acornfiresecurity.com 2.5.6 Relay Circuits Fault Output. Relay 1 is arranged for failsafe operation as standard. Section 8.8 The HS-5000 Series are equipped with two relay RELAY 1 RELAY 2 outputs. These are normally programmed to activate on Fault and Fire Alarm conditions respectively.
www.acornfiresecurity.com 2.5.9 Switch Inputs 2.5.9.1 Base Card PBUS SWITCH One Switch input is provided on the base card (I/P9) and up to eight key switch inputs (I/P1-8) are provided on the display card. These can be used for changing access level, performing “class change”...
www.acornfiresecurity.com 2.5.12 Routing Interface The Plug-In Routing Interface is used to output monitored signals to Fire Routing Equipment and Fault Routing Equipment or to Fire Protection Equipment. 2.5.12.1 Fire / Fault Routing Each function comprises of an output circuit and an input (confirmatory) circuit.
www.acornfiresecurity.com 2.5.13 VdS Interface The HSP-504 is a chassis mount interface it is used to connect the panel to dedicated equipment required in Germany and other markets. The interface provides input / output circuits for 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 connection to:...
www.acornfiresecurity.com 2.5.13.1 FAT / FBF Direct Connection The interface is compatible with IFAM FAT3000 and FBF2003 products using IHD protocol. Both the FAT and FBF can be directly connected to the interface card. When the FAT and FBF are closely coupled or included in a common housing, connect the FBF via the RS232 connections to the FAT.
www.acornfiresecurity.com 2.5.13.2 FAT / FBF Redundant Connection Where several FAT terminals need to be connected, or where a redundant connection is required from several control panels, connect the FAT units via a redundant ring. This requires the installation of an IFAM ADP-N3E Interface in one panel and (optionally) an IFAM ADP-N3S Interface in a second panel if required.
www.acornfiresecurity.com 2.5.13.4 ÜE Fire Routing The interface is compatible with routing equipment with a range of coil impedances from 200Ω- 5000Ω. If the ÜE output is not used, fit one of the supplied 4K7 resistors across terminals 12&13. 24VDC Power can be supplied to the routing Router equipment if required.
www.acornfiresecurity.com 3 Programming Introduction These instructions cover the configuration and programming of the panels. Where you see the “PC Only” symbol, these features can either only be set-up using the PC Configuration Tool or there are additional options that are only available via the PC Configuration Tool.
www.acornfiresecurity.com 3.1.4 Changing Text Descriptions Various parameters can have a text description defined. These include loop devices, zones, etc. The zone and device text descriptions will be shown on the display in the Fire Alarm, Fault and Warning Conditions, etc. to provide a quick and clear indication of the source of the problem. To change the text description, first highlight the text description within the appropriate programming option and then press the button.
www.acornfiresecurity.com 3.1.5 Numeric data entry Numbers are entered by moving to the required field, and then typing in the required number, followed by the button. If the number is entered incorrectly, press the ‘Esc’ button to restore the previous number. Level 3 Menu Functions The following table gives a list of the Level 3 Menu Functions, the sub-functions available within each main function and a brief description for each function.
www.acornfiresecurity.com Recommended Programming Procedure The main programming steps required will necessarily be different for each installation. However, the following is the minimum recommended. Step 1 – SET-UP, Define General Set-up Information (Phone Numbers, etc.). Step 2 – PASSWORDS, Define Level 2 and Level 3 Passwords as required. ...
www.acornfiresecurity.com 3.3.2.1 State This parameter shows the current operational status of the device. For example, this can show Normal, Fire Alarm, Device Missing, etc. This parameter cannot be changed. 3.3.2.2 Type This parameter shows the type of device learnt by the panel. For example, this can show Call Point, Multi-Sensor, ION Smoke, Heat, etc.
www.acornfiresecurity.com Action Description Fire Signal A Fire Alarm Condition will be generated whenever the input is active. Pre-Alarm A Pre-Alarm Condition will be generated whenever the input is active. Supervisory A Supervisory Condition will be generated whenever the input is active Create Alarm 1 An “Alarm 1”...
Page 43
www.acornfiresecurity.com 3.3.2.8.1 Mode: This option is shown on the display for specific device types only. Refer to the appropriate protocol application note for further information. 3.3.2.8.2 Delay The value in this field defines the delay from detecting an alarm to entering the alarm condition. The delay time can be changed in 1-second increments.
www.acornfiresecurity.com the same panel also require the same settings, then you only need to set them to SSM/Clock 2. If instead another Multi-Sensor requires a different setting, use a different SSM/Clock number. 3.3.2.9 O/P Group The Output Group assigned to the Sounder or Relay Devices determines the manner in which the outputs will operate when a fire alarm or other programmed condition occurs.
www.acornfiresecurity.com 3.3.3 Loops – Auto Learn 3.3.3.1 Normal Procedure / Initial learn The panel can automatically learn the presence or absence of devices at all addresses connected to the loop. When the Auto Learn option is selected, the panel starts searching each address on the loop to locate and find all of the devices connected.
www.acornfiresecurity.com ACCEPT NEW DEVICE REJECT NEW DEVICE ACCEPT ALL NEW DEVICES REJECT ALL NEW DEVICES Address 002 NEW DEVICE If the new device is accepted (or all new devices are accepted), the panel will configure the memory to register these devices. All data will be configured to initial settings for sensitivity threshold changes, text assignments, zone assignment, action, etc.
www.acornfiresecurity.com Item Description Last Activation The date and time that the device was last activated (e.g. smoke level detected is at pre-alarm or alarm levels or the last time that an output was turned on). Last Test The date and time that the device was last tested (e.g. smoke level detected is at pre-alarm or alarm levels or the last time that an output was turned on).
www.acornfiresecurity.com 3.3.8 Zones The Commission Zones option lists all the zones in use by this panel and allows the zone text description to be changed. [Commission Zones] Zone Location 0001 BASEMENT WEST 0002 RECEPTION 0015 EAST WING 0018 TOWER BLOCK To change the location text assigned to the Zone, press the button when the Zone Location Text is highlighted.
www.acornfiresecurity.com 3.3.12 View Options The View Menu Options are identical to those available during Level-2 operation – refer to User Manual for further information. 3.3.13 Passwords The panel provides up to 10 User Level-2 passwords and 2 Level-3 passwords. All of the passwords can be changed.
www.acornfiresecurity.com 3.3.16 EN54-13 The EN54-13 menu defines whether EN54-13 transmission path monitoring is in use and defines the actual load current (shown in milliamps) to be used in the calculation for each of the base card loop and sounder circuits. If enabled, the panel monitors the circuits to ensure that at the specified load current, the circuit can deliver the load current whilst still maintaining circuit device voltage compatibility levels via the transmission path resistance.
www.acornfiresecurity.com 3.3.17.3 Service Number The Service Number is the telephone number that is shown on the status display whenever a fault condition is accepted. To change the number, press the button when the option is highlighted. The number is entered using the text entry facility; refer to Section 3.1.4 for guidance on how to enter text.
www.acornfiresecurity.com Use the buttons to scroll through the list of options and press the button to confirm the selection. The device LED indicators will not blink if NONE is chosen or will blink if ALL is chosen. Note that only certain devices, such as Apollo Discovery, support this feature.
www.acornfiresecurity.com Press the button. A pop-up menu will be shown to confirm whether the configuration data shall be erased. 3.3.18 Display Depending on the physical mounted height of the panel, the contrast of the LCD may need adjusting to obtain optimum viewing. The display option permits the contrast adjustment of the LCD. [DISPLAY OPTIONS] ADJUST CONTRAST Press the button.
www.acornfiresecurity.com 3.3.19.1 AC Fail Delay The panel can be configured to delay the reporting of a loss of AC Mains supply (Address 14.0). The front panel Green Power LED will still immediately flash on the loss of the AC Supply, but the fault condition is only reported after the delay time (default 10s) has elapsed.
www.acornfiresecurity.com 3.3.20 Output Groups The “Cause and Effect” programming is a schedule of actions that will turn on one or more outputs dependant on a set of input events. The Outputs Option provides the means to create simple or complex “cause and effect” programming within the panel.
www.acornfiresecurity.com 3.3.20.2 Cause Each Output Group can be programmed to respond in a unique way to events from each individual zone. An input event may be a fire alarm condition or it may be a fault, disablement or other condition. A combination of criteria may also be applied to each zone. The Cause field determines what type of input event (or a combination of input events) will generate an output response for the selected input zone.
www.acornfiresecurity.com 3.3.20.3 Style The way in which an output turns on in response to a particular input event can be programmed. For example, an output may turn on immediately, it may turn on after a delay or it may pulse for a set time and then turn on.
www.acornfiresecurity.com Each input and output device can be individually programmed to use the investigation delay from the PC configuration software, together with the times appropriate to each stage of the delay. The user manual gives details of how the building occupier can turn the investigation delay feature on or off.
www.acornfiresecurity.com 4 Service and Maintenance Maintenance Schedule This equipment should be maintained in accordance with the regulations and codes appropriate to the country and location of installation. The following is recommended if no other regulations apply. 4.1.1 Daily Actions The site operator / user should perform the following checks and actions: a) The panel indicates normal operation.
www.acornfiresecurity.com Replacement of Components In general, all of the components parts used in the construction of the panel have been selected for long life and reliability. However, certain components may require to be changed on a regular service basis. The details of these are as follows: 4.2.1 Batteries...
www.acornfiresecurity.com 4.2.2 Liquid Crystal Display Expected Life: > 10 years Replacement Schedule: When the display becomes difficult to read. The display contrast will gradually fade with time. Manufacturer / Part Number: Replace the complete display / keyboard assembly. Spare part number MXS 504. 4.2.3 Spares Part Number...
www.acornfiresecurity.com 5 Appendices Appendix 1 – Forgotten Level 3 Password Should the Level-3 password be forgotten, contact Customer Support to obtain a temporary permit number to regain access to the panel programming functions. Customer Support will require a decryption key displayed by the panel. To obtain this number, attempt to gain access to the Level-3 Programming Functions entering “1”...
www.acornfiresecurity.com Appendix 2 – Recommended Fire Rated Cables The following table provides a list of suitable fire rated cables with standard (30 minute) and enhanced (120 minute) classification. Refer to Document No. 680-088 for an up to date list. Core Sizes (mm) 5839-1 Rated Manufacturer Cable Type...
www.acornfiresecurity.com 5.2.2 Sounder Circuit Lengths The voltage drop on each alarm circuit should be calculated to ensure that the minimum voltage at the end of the circuit exceeds the minimum required by each sounding device at the minimum alarm circuit output voltage. The voltage at the end of the circuit is given by: Minimum Alarm Voltage = V –...
www.acornfiresecurity.com Appendix 3 – Battery Standby Calculation Chart Use the following charts and associated notes to calculate the size of the batteries required to ensure operation of the installation in the event of AC Mains power failure. This chart is applicable to all panels except :HS-5100N, HS-5200N and HS-5400N Quiescent Load Fire Alarm Load...
www.acornfiresecurity.com Appendix 4 – Cause and Effect Programming Example 5.4.1 Introduction By default, all sounders and output devices will turn on immediately as soon as a fire is detected anywhere in the system. For example: Cause Effect Any Fire, Anywhere. ALL Output Devices will Turn ON Quite often an installation will require a more complex “Cause and Effect”...
www.acornfiresecurity.com 5.4.4 Output Group Programming To achieve the above cause and effect requirements, the three different Output Groups would be programmed and indicated on the panel as in the following display examples: Output Group 6 – Sounders on Floor 6: [Output Group 3.9% Mem used] [STYLE 02...
5.5 Appendix 5 – Other Useful Documents The following reference and application documents may be useful in the design, configuration and installation of the system. The latest versions are available from the Haes Systems Ltd web site (www.haes-systems.com) or in hard copy format from Sales. Document...
www.acornfiresecurity.com Appendix 6 –Network Design Principles This section gives recommendations on the design of the installation to cover specific EN54-2 requirements and typical national codes of practice. [EN54-2: 1997, Clause 13.7] Not more than 512 fire detectors and / or manual call points and their associated mandatory functions shall be affected as a result of a system fault in the C.I.E.
www.acornfiresecurity.com Appendix 7 – HS Series Product Capabilities / Max Limits This section gives details on the maximum capabilities for each of the products in the range. Some of the items can only be utilised via the PC CONFIG tool and these are annotated accordingly. Item Comments 5100...