To change the dependency mode type for the panel, enter the above code and press ENTER (panel is set
to type A by default).
The amber, fault LED 1 will pulse and the current setting will be indicated by a steady amber, fault LED as
per table below.
LED 1
No Dependency Mode
Use button 1 to move the pulsing amber LED to the required type as per above and press ENTER to select
it. The LED will change to a rapid pulse to indicate that it is now the current setting.
Type 'C' Configuration Option
In type 'C' Dependency Mode it is possible to select which outputs are delayed by the dependency.
Pressing button 4 will alternate between 'Sounders' and 'Aux' and all possible combinations using the
Sounder and Aux active LED to indicate the delay setting,
i.e. 'ON' = DELAYED.
Note:- Sounder = 4 conventional sounder circuits
Aux = Fire relay & switch negative outputs
Press and hold button 1 for 3 seconds to save the setting and exit the programming mode.
2
1
1
4
Select Zones For Dependency Mode
To select which zones should be included in the dependency mode, enter the above code and press
ENTER.
The amber, fault LED 1 will pulse and any zones that are currently set to dependency mode will be indicated
by a steady amber, fault LED.
Use button 1 to move the pulsing amber LED to the required zone(s) for setting and press ENTER to select.
The LED will change to a rapid pulse to indicate that the zone is now set to dependency mode. Pressing
ENTER again will de-select the zone and the LED will change back to a slow pulse.
Press and hold button 1 for 3 seconds to save the settings and exit the programming mode.
2
1
3
4
Set Timings For Dependency Mode B
There are two programmable timings for dependency mode B, the confirmation time
time
.
2
Enter the above code and press ENTER. The fire LED 1 will light indicating changing the timing for the
confirmation time, 1 - 4 minutes. Use button 1 to move to fire LED 2, for changing the timing for the auto
reset time (5 - 30 minutes).
Esento Marine 8-12 Installation, Commissioning & Operating Manual
LED 2
Type A
SETUP & PROGRAMMING
LED 3
Type B
Approved Document Ref: UI-ESEN12MAR-01 Issue 8.0