SETUP & PROGRAMMING
4
3
4
3
Comms PCB Output Functional Options
If a repeater Comms PCB (TPCA05) has been fitted to the panel, the 6, swtched -ve outputs on the PCB
can also be independently programmed with a custom response to; Silence Alarms (including, Silence
button or input programmed for remote Silence Alarms), Evacuate (including, Resound button, input
programmed for Evacuate or 220Ω 'Evacuate' call point), Class Change Input, Alert Input or during Zone
Delays.
Enter the above code, and press the ENTER button.
The zone 1 fire LED will light. This indicates the output to be programmed
as per the table below.
LED 1
OP 1
RESOUND
SILENCE
1
2
3
4
Disable
Test
Mute
Test
Mode
Mode
Buzzer
Lamps
Use button 1 to scroll to the function that requires editing for that output, inidicated by a pulsing fire LED
1 - 5 as per table below.
Fire LED
LED 1
(pulsing)
Resets on
Function
Silence
Alarms
Amber
fault LED
OFF
(default
setting)
Use button 2 to change the response for the output as per table above,
indicated by the amber, fault LED, ON, Pulsing or OFF. Then use button 1 to
move to the next function if required.
Press the ENTER button to return back to the output selection, indicated by a steady zone fire LED
When finished, press and hold Button 1 for 3 seconds to save setting and exit programming mode.
Esento Marine 8-12 Installation, Commissioning & Operating Manual
LED 2
LED 3
OP 2
OP 3
Use button 1 to move the fire LED to the output that requires editing.
RESET
With the required output for editing LED lit, press the ENTER button to
enter 'editing mode'.
ENTER
The fire zone 1 LED will now pulse to indicate setting the selected
output's response to the first function (Resets on Silence Alarms).
LED 2
LED 3
Activates
Activates
on
on Class
Evacuate
Change
OFF
OFF
Disable
Mode
LED 4
LED 5
LED 6
OP 4
OP 5
OP 6
LED 4
LED 5
Activates
Activates
During
on Alert
Delay
OFF
OFF
Approved Document Ref: UI-ESEN12MAR-01 Issue 8.0
44
RESOUND
SILENCE
RESET
1
2
3
4
ENTER
Test
Mute
Test
Mode
Buzzer
Lamps
LED 6
Follow
Muster
Alarm
OFF
RESOUND
SILENCE
1
2
3
Disable
Test
Mute
Mode
Mode
Buzzer
Lamps
RESET
4
ENTER
Test