SETUP & PROGRAMMING
4
1
4
1
Input Function Settings
The panel has two inputs, located on the main circuit board, Class Change (CC) and Alert (PUL). Switching
a negative voltage into these inputs will cause the alarm sounders to operate. The Class Change input
(CC) will cause the alarms to sound
continously and the Alert input
(PUL) will cause the alarms to pulse.
Either or both of these inputs can
be programmed to have a different
function.
The available functions are:
Class Change (continous
sounder operation).
Alert (pulsing sounder
operation).
Evacuate (a latching input which activates all the alarms and shows a general fire indication on the
panel).
Silence (for remote silence alarms control).
Reset (for remote reset control).
Fire Zone 12 (a non latching input which indicates zone 12 fire LED).
Fault Zone 12 (a non latching input which indicates zone 12 fault LED).
Input activates Muster Alarm signal.
To change the default function of the inputs, enter the above code
and press ENTER. The zone 1 fire LED will illuminate. This indicates
setting the function of the CC input. Use button 1 to move to zone
2 fire LED for setting the function of the PUL input and then back to
zone 1 again.
The current setting for the input will be indicated by the amber, fault
LEDs as per table below.
With the required fire LED lit, as per above, press the ENTER button to enter 'editing mode'. The fire zone
1 LED will now pulse to indicate function 1 (Class Change).
RESOUND
SILENCE
RESET
1
2
3
4
Disable
Test
Mute
Test
Mode
Mode
Buzzer
Lamps
LED 1
LED 2
Class
Alert
Change
Press the ENTER button again to return to input selection.
When finished, press and hold Button 1 for 3 seconds to save setting and exit programming mode
Enter the next programming code or disable the controls and return DIL switch 6 to 'OFF'.
Esento Marine 8-12 Installation, Commissioning & Operating Manual
PSU
28V 0V
@ +
-
-
+
Now use button 1 to move the pulsing fire LED
to the required setting as per the table below,
then use button 2 to select the function. The
amber, fault LED will move to indicate the new
ENTER
current setting.
LED 3
LED 4
Remote
Evacuate
Silence
Alarms
CC
PUL
-IP -IP
FIRE
FAULT
FR
FLT
CC
PUL
C NC NO
C NC NO
-OP -OP -IP -IP
LED 5
LED 6
Remote
Fire Zone
Reset
12
Approved Document Ref: UI-ESEN12MAR-01 Issue 8.0
36
SNDR1 SNDR2
ZONE1 ZONE2 ZONE3 ZONE4
+ -
+ -
+ -
+ - + -
RESOUND
SILENCE
RESET
1
2
3
4
Disable
Test
Mute
Test
Mode
Mode
Buzzer
Lamps
RESOUND
SILENCE
1
2
3
Disable
Test
Mute
Mode
Mode
Buzzer
LED 7
LED 8
Fault Zone
Muster
12
Alarm
+ -
ENTER
RESET
4
ENTER
Test
Lamps