Output Programmability & Miscellaneous
All of the relays & outputs on the control panel's main circuit board (TPC-A01) have default functions, i.e.
operate on fire or fault. The function for each of these outputs, however, can be changed. The outputs can
also be programmed to have different responses for selected zones.
Before any programming can be applied to the main circuit board outputs, they must first be made
programmable using this mode.
Mode 4-1-4-2 also has 2 other miscellaneous functions, these are:
Set Fault Latching - This sets the latching of all faults on the panel. A useful tool for capturing any random
or intermittent faults.
Invert Fault Output - The switched -ve fault output on the main circuit board usually appears when a fault
is present. This can be inverted so that the output is constant and dissapears when a fault occurs, for fail
safe operation.
To set either of the two miscellaneous options above or to make outputs programmable, enter the above
code and press ENTER.
The fire zone 1 LED will now pulse to indicate the setting of attribute 1 (fault latching).
Use button 1 to scroll to the attribute that requires setting,
inidicated by a pulsing fire LED 1 - 6 as per table below.
The setting of the attribute is indicated by the amber, fault
LED, ON or OFF.
Fire LED
LED 1
(pulsing)
Fault
Attribute
latching
RESOUND
SILENCE
1
2
3
4
Disable
Test
Mute
Test
Mode
Mode
Buzzer
Lamps
When finished, press and hold Button 1 for 3 seconds to save setting and exit programming mode
Enter the next programming code or disable the controls and return DIL switch 6 to 'OFF'.
Esento Marine 8-12 Installation, Commissioning & Operating Manual
LED 2
LED 3
Invert Fault
Fault Relay
Output
Programmable
With the required fire LED pulsing, use button 2 to switch the attribute
RESET
ON or OFF (amber, fault LED, ON or OFF).
ENTER
SETUP & PROGRAMMING
Disable
Mode
LED 4
LED 5
Fault Output
Fire Relay
Programmable
Programmable
Approved Document Ref: UI-ESEN12MAR-01 Issue 8.0
37
RESOUND
SILENCE
RESET
1
2
3
4
ENTER
Test
Mute
Test
Mode
Buzzer
Lamps
LED 6
Fire Output
Programmable

Hide quick links:

Advertisement

Table of Contents
loading

This manual is also suitable for:

Esento esen-12mar0832-med-1086

Table of Contents