Haes ESENTO ESEN-8MAR Installation, Commissioning & Operating Manual page 43

Marine approved 8 - 12 zone conventional control panel
Table of Contents

Advertisement

4
3
4
4
To programme each of the conventional sounder circuits on the main circuit board and high spec zone
extension cards with same custom reponses as above, the process is exactly the same but using the code
4-3-4-4.
I.e. Use button 1 to select the sounder circuit first (indicated by a steady fire zone LED) as per table below.
LED 1
LED 2
SNDR1
SNDR2
(Main
(Main
PCB)
PCB)
Press ENTER and then use button 1 to select the function that requires editing for that sounder circuit
(indicated by a pulsing fire zone LED) as per the sounder CCT function table in the Twin Wire settings
above.
Use button 2 to edit the response indicated by the amber, fault LED, ON or OFF.
Press the ENTER button to return back to the sounder circuit selection, indicated by a steady zone fire
LED.
When finished, press and hold Button 1 for 3 seconds to save setting and exit programming mode.
Esento Marine 8-12 Installation, Commissioning & Operating Manual
Conventional Sounder Circuit Functional Options
LED 3
SNDR A.
Zone ext card
1 (Zones 5
- 8)
SETUP & PROGRAMMING
LED 4
LED 5
SNDR B.
SNDR A.
Zone ext card
Zone ext card
1 (Zones 5
2 (Zones 9 -
- 8)
12)
Approved Document Ref: UI-ESEN12MAR-01 Issue 8.0
41
LED 6
SNDR B.
Zone ext card
2 (Zones 9 -
12)