SETUP & PROGRAMMING
1
2
2
2
This option is used to select zones for activation of a muster alarm signal. A muster alarm is defined as 7
short blasts of the sounders, followed by 1 long blast. This is repeated until silenced. The activated muster
alarm zone will show a fire indication at the panel but no common fire LED. The panels outputs can be
programmed to respond to a muster alarm using seperate option codes.
A second setting is provided to enable the panels 'RESOUND' button to activate the muster alarm signal.
Note: With panel software V4.1 and above, muster alarm will have priority over any new fire alarms by
default. It is possible to make fire a higher priority using option 3.
Enter the above code and press
the ENTER button.
The zone 1 fire LED will be on
steady. Use button 1 to toggle
between steady fire LEDs 1, for
setting muster alam zones, 2, for setting RESOUND button to activate muster alarm, 3, for changing
muster alarm priority or 4, for Muster Alarm Synchronisation.
Set Muster Alarm Zones [LED 1]
With the zone 1 fire LED lit press the ENTER button and the LED will pulse to indicate setting zone 1 to
muster alarm. Use button 1 to move the pulsing fire LED to the required zone and then use button 2 to
change the setting, indicated by the amber fault LED ON or OFF. Any or all zones may be set for muster
alarm.
ON = muster alarm zone, OFF = standard.
Set RESOUND Button Operation For Muster Alarm [LED 2]
With the zone 2 fire LED lit press the ENTER button. Fire LED 2 will now pulse to indicate editing mode.
Use button 2 to toggle the option on or off, indicated by zone 1 amber fault LED ON or OFF.
ON = RESOUND button activates muster alarm, OFF = RESOUND button activates evacuate (default).
Set Fire As Priority Over Muster Alarm [LED 3]
With the zone 3 fire LED lit press the ENTER button. Fire LED 3 will now pulse to indicate editing mode.
Use button 2 to toggle the option on or off, indicated by zone 1 amber fault LED ON or OFF.
OFF = muster alarm has priority, ON = fire has priority.
Esento Marine 8-12 Installation, Commissioning & Operating Manual
Muster Alarm Signal.
LED 1
Select
muster
alarm zones
LED 2
LED 3
Set
Set muster
RESOUND
alarm
button
priority
OFF
Approved Document Ref: UI-ESEN12MAR-01 Issue 8.0
22
LED 4
LED 5
Muster
Set VDR
synch
card
mode
Presence
(slave)