Chimney Installation - Pacific energy ALT 1.2 Installation And Operating Instructions Manual

Table of Contents

Advertisement

Chimney Installation

Ensure that the Masonry
chimney meets all National
Fire Protection Association
and local building codes.
Have the chimney cleaned
and inspected by a
professional to ensure
there are no cracks, weak
mortar or other signs of
deterioration. See pipe
manufacturers installation
instructions for further
information
6.
If a roof or ceiling support is used in the installation, you will find the chimney manufacturer's complete
instructions packed with the roof support.
7.
To start installing smoke pipe (chimney connector), slip crimped edge of the pipe inside the stove collar. Use
holes provided in collar to secure pipe with three screws.
8.
Install the remaining lengths of pipe one on top of the other to the finished height of the chimney connector and
secure to each other.
9.
Assemble chimney sections so the finished length is resting on the support and protruding through the roof.
Avoid having joints between ceiling and roof. Brace chimney as required by Chimney Manufactures instructions.
Install radiation shield.
10.
Assemble flashing and storm collar and be sure to maintain the vapour barrier at this point. (Seal securely.)
Attach rain cap and check flashing for leaks.
210618-28_ALT 1.2
Ensure that the Masonry chimney
meets all National Fire Protection
Association and local building codes.
Have the chimney cleaned and
inspected by a professional to ensure
there are no cracks, weak mortar or
other signs of deterioration. See pipe
manufacturers installation instructions
for further information.
Minimum 7' (2.1m.)
Ceiling Height
Non-combustible
oor protector
*3" diameter air inlet with rodent screen
*If the crawl space is well ventilated it
is not necessary to extend air inlet to
outside
Figure 17: Alt 1.2 Venting to a masonary chimney.
Fireclay Flue liner
Concrete cap
Chimney
As per local
and Federal codes
Chimney Connector
12"(305mm)
Minimum rst
section of pipe
48"
(1.2m)
17
Approved
Through - Wall
Installation
Hooded vent or
90 elbow turned down
5055.7298-A