Bench Top Configuration - Emerson Rosemount 648 Reference Manual

Wireless temperature transmitter with rosemount x-well technology
Hide thumbs Also See for Rosemount 648:
Table of Contents

Advertisement

Reference Manual
00809-0200-4648
2.4

Bench top configuration

Bench top configuration consists of testing the transmitter and verifying transmitter
configuration data. The transmitter must be configured before installation, which may be
performed either directly or remotely. Direct configuration can be performed using a Field
Communicator, AMS Device Manager, AMS Wireless Configurator, or any WirelessHART
Communicator. Remote configuration can be performed using AMS Device Manager, AMS
Wireless Configurator, or the Wireless Gateway.
The power module must be installed to provide power to the transmitter for
configuration. To communicate to the transmitter, begin by removing the power module-
side housing cover, indicated as "Field terminals" by text located on the side of the device.
This will expose the terminal block and HART Communication terminals, which are labeled
"COMM". Connect the power module to supply power for configuration. See
Figure 2-7: Connection Diagram for Rosemount 648 Wireless and Field
Communicator
2.4.1
Field Communicator
When performing device configuration directly, connect the bench equipment as shown
in
Figure 2-7
When using a Field Communicator, any configuration changes must be sent to the
transmitter by using the Send key (F2).
The Field Communicator will search for a HART
connection is made. If the Field Communicator fails to connect, it will indicate that no
device was found. If this occurs, refer to Troubleshooting.
Note
For HART Wireless transmitter communication via a Field Communicator, a Rosemount
648 Wireless Device Dashboard (DD) is required. Rosemount 648 Wireless Transmitters
equipped with Rosemount X-well Technology requires DD revision 648 Dev. 4 Rev. 1 or
higher to view Rosemount X-well functionality. To obtain the latest DD, visit
Emerson.com/Field-Communicator.