Quick Installation Guide
00825-0300-4728, Rev AA
July 2010
Rosemount 644H Profibus PA Temperature
Transmitters
www.rosemount.com
¢00825-0100-4728w¤
Step 1: Mount the Transmitter
Step 2: Wire and Apply Power
Step 3: Verify Tagging
Step 4: Transmitter Configuration
Product Certifications
Start
End
Rosemount 644

Advertisement

Table of Contents
loading

Summary of Contents for Emerson Rosemount 644H Profibus

  • Page 1 Quick Installation Guide 00825-0300-4728, Rev AA Rosemount 644 July 2010 Rosemount 644H Profibus PA Temperature Transmitters Start Step 1: Mount the Transmitter Step 2: Wire and Apply Power Step 3: Verify Tagging Step 4: Transmitter Configuration Product Certifications www.rosemount.com ¢00825-0100-4728w¤...
  • Page 2: Important Notice

    8200 Market Boulevard Chanhassen, MN USA 55317 T (US) (800) 999-9307 T (Intnl) (952) 906-8888 F (952) 949-7001 Emerson Process Management GmbH & Co. OHG Frankenstrasse 21 63791 Karlstein Germany T 49 (6188) 992 0 F 49 (6188) 992 112...
  • Page 3: Step 1: Mount The Transmitter

    Quick Installation Guide 00825-0300-4728, Rev AA Rosemount 644 July 2010 1: M OUNT THE RANSMITTER Mount the transmitter at a high point in the conduit run to prevent moisture from draining into the transmitter housing. Typical Connection Head Installation Head Mount Transmitter with DIN Plate Style Sensor 1.
  • Page 4 Quick Installation Guide 00825-0300-4728, Rev AA Rosemount 644 July 2010 CONTINUED Typical Universal Head Installation Head Mount Transmitter with Threaded Sensor 1. Attach the thermowell to the pipe or process container wall. Install and tighten thermowells before applying process pressure. 2.
  • Page 5: Step 2: Wire And Apply Power

    * The transmitters must be configured for at least a 3-wire RTD in order to recognize an RTD with a compensation loop. ** Emerson Process Management provides 4-wire sensors for all single element RTDs. Use these RTDs in 3-wire configurations by leaving the unneeded leads disconnected and insulated with electrical...
  • Page 6: Ground The Transmitter

    Quick Installation Guide 00825-0300-4728, Rev AA Rosemount 644 July 2010 CONTINUED Typical Configuration for Profibus Networking Profibus DP RS-485 up to 12 MBd Profibus Transmitter DP/PA Coupler PROFIBUS Power/ Class 2 Master Signal (Configuration Wiring Tool) Profibus PA MBP-IS at 31.25KBd Terminators 6234 ft.
  • Page 7 Quick Installation Guide 00825-0300-4728, Rev AA Rosemount 644 July 2010 CONTINUED Option 2: 1. Connect signal wiring shield to the sensor wiring shield. 2. Ensure the two shields are tied together and electrically isolated from the transmitter housing. 3. Ground shield at the power supply end only. 4.
  • Page 8: Step 3: Verify Tagging

    Quick Installation Guide 00825-0300-4728, Rev AA Rosemount 644 July 2010 3: V ERIFY AGGING Commissioning (Paper) Tag To identify which device is at a particular location use the removable tag provided with the transmitter. COMMISSIONING TAG Ensure that the physical device tag (PD Tag field) is IDENT_NUMBERS 4153 [9700] properly entered in both places on the removable Device Address: ##...
  • Page 9 Quick Installation Guide 00825-0300-4728, Rev AA Rosemount 644 July 2010 Transducer Function Block This block contains temperature measurement data for the sensor and the terminal temperature. It also includes information about sensor types, engineering units and diagnostics. At a minimum, verify the parameters in Table 1. Table 1.
  • Page 10: Approved Manufacturing Locations

    RODUCT ERTIFICATIONS Approved Manufacturing Locations Emerson Process Management Rosemount Division. – Chanhassen, Minnesota, USA Rosemount Temperature GmbH – Germany Emerson Process Management Asia Pacific – Singapore European Union Directive Information The EC declaration of conformity for all applicable European directives for this product can be found on the Rosemount website at www.rosemount.com.
  • Page 11: Hazardous Locations Certificates

    Quick Installation Guide 00825-0300-4728, Rev AA Rosemount 644 July 2010 Hazardous Locations Certificates North American Certifications Factory Mutual (FM) Approvals FM Intrinsically Safe Intrinsically Safe FISCO for use in Class I, II, III, Division 1, Groups A, B, C, D, E, F, and G;...
  • Page 12 Quick Installation Guide 00825-0300-4728, Rev AA Rosemount 644 July 2010 European Certifications E1 ATEX Flame-Proof Certificate Number: KEMA99ATEX8715X ATEX Marking: II 2 G 1180 Ex d IIC T6 (–40 °C ≤ T ≤ 65 °C) U = 55 Vdc Special Conditions for Safe Use (X): For information on the dimensions of the flameproof joints the manufacturer shall be contacted.
  • Page 13: Iecex Certifications

    Quick Installation Guide 00825-0300-4728, Rev AA Rosemount 644 July 2010 N1 ATEX Type n Certificate Number: BAS00ATEX3145 ATEX Marking: II 3 G T5 (-40 °C ≤ T ≤ 70 °C) Ex nL IIC = 45 V NC ATEX Type n Component Certificate Number: BAS99ATEX3084U ATEX Marking: II 3 G...
  • Page 14 Quick Installation Guide 00825-0300-4728, Rev AA Rosemount 644 July 2010 Special Conditions for Safe Use (X): 1. The apparatus must be installed in an enclosure which affords it a degree of protection of at least IP20. 2. Non-metallic enclosures must have a surface resistance of less than 1 G ; light alloy or zirconium enclosures must be protected from impact and friction when installed.
  • Page 15 Quick Installation Guide 00825-0300-4728, Rev AA Rosemount 644 July 2010 Combination Approvals K5 Combination of I5 and E5. Russian GOST Certifications PPC BA-13006: 0 Ex ia IIC T4/T5/T6 Kazakhstan GOST Pattern approval Certificate for Measuring Instruments See Certificate Ukraine GOST Pattern Approval for Measuring Instruments See Certificate...
  • Page 16: Ec Declaration Of Conformity

    Quick Installation Guide 00825-0300-4728, Rev AA Rosemount 644 July 2010 EC Declaration of Conformity No: RMD 1016 Rev. F Rosemount Inc. 8200 Market Boulevard Chanhassen, MN 55317-6985 declare under our sole responsibility that the product, Models 644 Smart Temperature Transmitter (Hart & Fieldbus) manufactured by, Rosemount Inc.
  • Page 17 Quick Installation Guide 00825-0300-4728, Rev AA Rosemount 644 July 2010 Schedule EC Declaration of Conformity RMD 1016 Rev. F EMC Directive (2004/108/EC) Models 644HA Smart Temperature Transmitters (Hart) EN 61326: 1997 + A1/A2/A3 -- Industrial Models 644HF Smart Temperature Transmitters (Fieldbus) EN 61326: 1997 + A1/A2/A3 -- Industrial Models 644RA Smart Temperature Transmitters (Hart) EN 61326: 1997 + A1/A2/A3 -- Industrial...
  • Page 18 Quick Installation Guide 00825-0300-4728, Rev AA Rosemount 644 July 2010 Models 644HF Smart Temperature Transmitters (Fieldbus) - continued EEx d IIC: KEMA 99ATEX8715 -- Flameproof Certificate EN50014: 1997 + A1, A2, prA3, EN50018: 1994 + prA1…prA3 Models 644RA Smart Temperature Transmitters (Hart) Ex ia IIC: BAS00ATEX1033X -- Intrinsically Safe Certificate EN 60079-0: 2006, EN 60079-11: 2007...