Control Output Type
£
Discrete 0 or 12VDC digital, Pulse, or PWM output controlling a
12VDC relay. Maximum 60 mA (minimum load resistance 200Ω).
£
0 to 20mA current output – set the DIP switch to 0-20mA.
£
See DIP Switch and Jumper Identification and Configuration on page
5 for more information about how to set the DIP Switch.
£
0 to 10VDC voltage output.
£
0 to 10VDC voltage output controlling an analog actuator that is pow-
ered by an external 24VAC power source.
£
24VAC externally-powered triac output controlling a relay
£
24VAC externally-powered triac output controlling a floating actuator
1. Maximum output current for all digital triac outputs is 0.5A continuous or 1A @ 15% duty cycle for a 10-minute period.
£
Line voltage powered form-C relay output, 0-277VAC / 0-30 VDC, 10A
maximum. For example, 120/240VAC controlling a 3 phase motor
contactor.
£
The line voltage must to be protected by a 10A Circuit breaker to pro-
tect the relay contact output against short circuit/overload conditions.
£
A single 10 amp circuit breaker can be used to protect two or more re-
lay outputs if all connected loads are on the same phase and the total
maximum current to all loads is less than 10A.
SELV circuit cannot be used on a relay output next to another relay
output used with Hazardous voltages (120-240VAC for example).
A Line-to-Line power source can be used only if the maximum Line-
to-Neutral Voltage is less than 120VAC.
Table 2: ECY IO Module Output Wiring
ECY IO mod-
ules' Output
Designation
£
UOx
£
UOx
£
UOx
£
UOx
1
.
£
DOx
(DOT
model)
1
£
.
DOx
(DOT
model)
£
DOx
(DOR
model)
Neutral
Output Connection Diagram
UOx
From
Digital
Output
COM
From Digital-To-
Analog Output
UOx
Current Output
COM
Option Enabled
UOx
From Digital-
To-Analog
Output
COM
UOx
From Digital-
To-Analog
Output
COM
DOx
From
Control
Cx-x
Logic
AC
DOx
From
Cx-x
Control
DOx
Logic
Line-to-Neutral AC Power Source
Line
Circuit
Breaker, 10 A
Maximum
NCx
Cx
NOx
From
Control
Logic
Line-to-Line AC Power Source
Line
Double Circuit
Breaker, 10 A
Maximum
NCx
Cx
NOx
From
Control
Logic
A1
A2
12VDC Relay
0-20mA
Common
0-10V
Common
Actuator
0-10V
~ or +
24VAC
or -
A1
A2
24VAC Relay
Actuator
~
24VAC
~
Neutral
A1
M
A2
3 Ø Contactor
Line
A1
M
A2
3 Ø Contactor
15 / 22