Each ECY IO module has a number of physical connections for inputs and/or outputs. These inputs and outputs are labelled on the ECY IO modules ac-
cording to the tables below. Input and output options must be configured properly in EC-gfxProgram to ensure correct input readings and output values.
The controller's license may have separate limits that reduce the availability of certain options.
ECY IO Modules
Inputs
ECY-8UI
8
ECY-16DI
16 DIx DIx DIx
ECY-6UO
ECY-6UO-HOA
ECY-8DOR
ECY-8DOR-HOA
ECY-4UI4UO
4
ECY-4UI4UO-HOA
4
ECY-8UI6UO
8
ECY-8UI6UO-HOA
8
ECY-8UI6DOT
8
ECY-8UI6DOT-HOA
8
1.
An on-board 18VDC power supply can provide the necessary power for 20mA current loop sensor operation. The 0 to 20mA current loop input option is individually selected through an on-board DIP
switch setting.
2.
0 to 10VDC is available on UO1 to UO6. 0 to 20 mA is available on UO1, UO2, and UO3; this option is individually selected through an on-board DIP switch setting.
Input Wiring
Input options must be properly configured in EC- gfx Program to ensure correct input readings. The table below shows the ECY IO modules' input desig-
nation for each IO model. For terminal block connector wiring best practices, see
follows.
Before connecting a sensor to the controller, refer to the installation guide of the equipment manufacturer.
£
For a wire length less than 75' (23m), either a shielded or unshielded 18AWG wire may be used.
£
For a wire up to 200' (61m) long, a shielded 18AWG wire is recommended.
£
The shield of the wire should be grounded on the controller side only and the shield length should be kept