SAEx 07.2
SAEx 16.2 / SAREx 07.2
9.4.
Intermediate positions: set
Information
9.4.1.
Running direction CLOSE (black section): set
SAREx 16.2
6.
As soon as the pointer [5] moves to mark [6]: Stop turning and release setting
spindle.
The end position OPEN setting is complete.
7.
If you override the tripping point inadvertently (ratchet click is heard after the
pointer has snapped): Continue turning the setting spindle in the same direction
and repeat setting process.
Option
Actuators equipped with DUO limit switches contain two intermediate position switches.
Intermediate switches may be set for either running direction.
Figure 22: Setting components for limit switches
Closed section (black):
[1]
Setting spindle: Running direction CLOSE
[2]
Pointer: Running direction CLOSE
[3]
Mark: Intermediate position CLOSED is set
Open section (white):
[4]
Setting spindle: Running direction OPEN
[5]
Pointer: Running direction OPEN
[6]
Mark: Intermediate position OPEN is set
After 177 revolutions of the actuator (control unit for 2
lutions of the actuator (control unit for 2
change contact.
1.
Move valve in direction CLOSE to desired intermediate position.
2.
If you override the tripping point inadvertently: Turn valve in opposite direction and
approach intermediate position again in direction CLOSE.
Information: Always approach the intermediate position in the same direction as
in later electrical operation.
3.
Press down and turn setting spindle [1] with screw driver in direction of the arrow
and observe the pointer [2]: While a ratchet click is felt and heard, the pointer [2]
moves 90° every time.
4.
As soon as the pointer [2] is 90° from mark [3]: Continue turning slowly.
500 turns/stroke) or 1,769 revo-
5,000 turns/stroke), the intermediate switches
Commissioning