8.

Signals

8.1.

Feedback signals from actuator

Information
Table 6:
Feedback signal
End position OPEN/CLOSED
reached
Intermediate position reached (op-
tion)
Torque OPEN/CLOSED reached
Motor protection tripped
Running indication (option)
Position feedback signal, (option)
Manual operation active (option)
SAREx 16.2
The switches can be provided as single switches (1 NC and 1 NO), as tandem switches
(2 NC and 2 NO) or as triple switches (3 NC and 3 NO). The precise version is indicated
in the terminal plan or on the order-related technical data sheet.
Type and designation in wiring diagram
Setting via limit switches
Switches: 2 NC and 2 NO (standard)
LSC
Limit switch, closing, clockwise rotation
LSO
Limit switch, opening, counterclockwise rotation
Setting via DUO limit switches
Switches: 1 NC and 1 NO (standard)
LSA
DUO limit switch, clockwise rotation
LSB
DUO limit switch, counterclockwise rotation
Setting via torque switches
Switches: 1 NC and 1 NO (standard)
TSC
Torque switch, closing, clockwise rotation
TSO
Torque switch, opening, counterclockwise rotation
Thermal switches
F1, Th
Thermal switches
Switches: 1 NC (standard)
S5, BL
Blinker transmitter
Depending on version either with potentiometer or electronic position transmitter EWG/RWG
R2
Potentiometer
R2/2
Potentiometer in tandem arrangement (option)
B1/B2, EWG/RWG
3-wire or 4-wire system (0/4 20 mA)
B3/B4, EWG/RWG
2-wire system (4
Switches
20 mA)
Signals
27

Advertisement