Switch Compartment: Close - AUMA SAEx 07.2 Operation Manual

Multi-turn actuators
Hide thumbs Also See for SAEx 07.2:
Table of Contents

Advertisement

SAEx 07.2
SAEx 16.2 / SAREx 07.2
9.10.

Switch compartment: close

SAREx 16.2
3.
Turn lower indicator disc until symbol
on the cover.
4.
Move actuator to end position OPEN.
5.
Hold lower indicator disc in position and turn upper disc with symbol
until it is in alignment with the mark
6.
Move valve to end position CLOSED again.
7.
Check settings:
If the symbol
(CLOSED) is no longer in alignment with mark
7.1 Repeat setting procedure.
7.2 Check whether the appropriate reduction gearing has been selected, if required.
Danger of corrosion due to damage to paint finish!
Touch up damage to paint finish after work on the device.
1.
Clean sealing faces of housing and cover.
2.
Preserve joint surfaces with an acid-free corrosion protection agent.
3.
Check whether O-ring [3] is in good condition, replace if damaged.
4.
Apply a thin film of non-acidic grease (e.g. petroleum jelly) to the O-ring and insert
it correctly.
Figure 28:
(CLOSED) is in alignment with the mark
on the cover.
Commissioning
(OPEN)
on the cover:
39