Siemens SIMATIC ET 200S Manual page 376

Distributed i/o system
Hide thumbs Also See for SIMATIC ET 200S:
Table of Contents

Advertisement

Digital Electronic Modules
Technical specifications
Dimensions and weight
Dimensions W H D
(mm)
Weight
Data for specific modules
Supports clocked operation
Number of outputs
Length of cable
Unshielded
Shielded
Voltages, currents, potentials
Rated supply voltage L+
(from the power module)
Reverse polarity protection
Current per channel
Up to 50 °C
Up to 60 °C
Isolation
Between the channels
Between the channels
and backplane bus
Between the channels
and supply voltage
Between the supply
voltage and backplane
bus
Permissible potential diffe-
rence
Between the supply
voltage and backplane
bus
Between channels and
backplane bus
Between the channels
and supply voltage
12-80
15 81 52
Approx. 50 g
No
2
Max. 600 m
Max. 1000 m
24 VDC
Yes
Max. 5 A
Max. 4 A
Yes
Yes
Yes
Yes
75 VDC, 60 VAC
240 VAC
240 VAC
Insulation tested
Between the supply
voltage and backplane
bus
Between channels and
backplane bus
Between the channels
and supply voltage
Current consumption
From the power supply
L+
Power dissipation of the
module
Status, interrupts, diagnostics
Status display
Diagnostic functions
Data for selecting an actuator
Output current
Continuous thermal
current
Min. load current
Min. voltage
Connecting two outputs in
parallel
For redundant triggering
of a load
To increase
performance
Control of a digital input
Switch rate
For resistive load
With inductive load
For lamp load
Limitation (internal) of the
voltage induced on circuit
interruption
Short-circuit protection of
1)
the output
1)
The relay outputs must be protected by means
of an external safety fuse (6 A, quick-response).
ET 200S Distributed I/O System
Yes
500 VDC
1500 VAC
1500 VAC
Max. 30 mA
Typ. 0.6 W
Green LED per
channel
No
Max. 5 A
8 mA
17 V
No
No
Yes
2 Hz
0.5 Hz
2 Hz
No
No
EWA-4NEB780602402-09