Siemens SIMATIC ET 200S Manual page 159

Distributed i/o system
Hide thumbs Also See for SIMATIC ET 200S:
Table of Contents

Advertisement

Evaluating hardware interrupts with STEP 7
In the event of a hardware interrupt, the CPU interrupts the processing of the user
program and processes the process interrupt block OB 40 instead.
The module channel that triggered the hardware interrupt is entered in the start
information of OB 40 in the OB40_POINT_ADDR variable. In the figures below you
will find the assignment to the bits of the local double word 8.
Hardware interrupts in the case of:
2DI 24 VDC High Feature and 4DI 24 VDC High Feature electronic modules:
LB 8
31 30 29 28 27 26
1
Rising edge: Channel 3
Figure 6-19
Start information of OB 40: Which event triggered a hardware interrupt with digital input
modules
Hardware interrupts in the case of:
2AI U High Speed, 2AI I 2WIRE High Speed, and 2AI I 4WIRE High Speed
electronic modules:
LB 8
31 30 29 28 27 26
Figure 6-20
Start information of OB 40: Which event triggered a hardware interrupt with analog input
modules
You will find a description of the OBs 40 in the reference manual System and
Standard Functions.
Triggering of an insert/remove-module interrupt
Insert/remove-module interrupts are supported in DPV1 operation. The CPU
interrupts processing of the user program and processes the diagnostic block
OB83 instead. The result that led to the triggering of the interrupt is entered in the
start information of OB83.
ET 200S Distributed I/O System
EWA-4NEB780602402-09
LB 9
LB 10
25 24
1
1
1
Rising edge: Channel 0
Rising edge: Channel 1
Rising edge: Channel 2
LB 9
25 24
23 22 21 20 19 18
1
1
Lower limit value violated: Channel 0
Upper limit value violated: Channel 1
Commissioning and Diagnostics
LB 11
1
0
Bit no.
LD 8
2DI
LB 10
LB 11
17 16
1
1
Lower limit value violated: Channel 0
Upper limit value violated: Channel 1
4DI
1
Bit no.
0
LD 8
6-25