Siemens SIMATIC ET 200S Manual page 285

Distributed i/o system
Hide thumbs Also See for SIMATIC ET 200S:
Table of Contents

Advertisement

11.2
PM-E 24 VDC power module (6ES7138-4CA00-0AA0)
Order number
6ES7138-4CA00-0AA0
Features
• The PM-E 24 VDC power module monitors the supply voltage for all the
electronic modules in the potential group. The supply voltage is fed in by means
of the TM-P terminal module.
• You can use any electronic module in the potential group of the PM-E 24 VDC
power module except the 2DI 120 VAC Standard, 2DI 230 VAC Standard and
2DO 24–230 VAC/1 A.
Caution
!
Only connect the specified rated load voltage of 24 VDC to the TM-P terminal
module of the power module.
The connected rated load voltage must correspond to the supply voltage of the
electronic modules in the potential group.
• The current status of the power module is stored in the status byte in the
process input image (PII). This is updated irrespective of whether the "No Load
Voltage" diagnosis has been enabled (see Appendix C).
ET 200S Distributed I/O System
EWA-4NEB780602402-09
Power Modules
11-3

Advertisement

Table of Contents
loading

Table of Contents