Analog Electronic Modules
Table 13-45 Terminal assignment of the 2AI RTD High Feature, continued
View
TM-E15S24-01 and 2AI RTD High Feature
CH0
CH1
M
M
0+
1+
1
5
M
M
0–
1–
2
6
I
I
C0+
C1+
3
7
I
I
C0–
C1–
4
8
TM-E15S26-A1 and 2AI RTD High Feature
CH0
CH1
M
M
0+
1+
1
5
M
M
0–
1–
2
6
I
I
C0+
C1+
3
7
I
I
C0–
C1–
4
8
A
A
AUX1
AUX1
4
8
A
A
AUX1
AUX1
3
7
13-82
Terminal assignment
2 conductors 3 conductors
2 conductors 3 conductors
Channel 0: Terminals 1 to 4
Channel 1: Terminals 5 to 8
M+: Measuring line (positive)
4 conductors
I
: Constant-current line
C–
(negative)
M–: Measuring line (negative)
I
: Constant-current line
C+
(positive)
Channel 0: Terminals 1 to A3
Channel 1: Terminals 5 to A7
M+: Measuring line (positive)
4 conductors
I
: Constant-current line
C–
(negative)
M–: Measuring line (negative)
I
: Constant-current line
C+
(positive)