Installing The Shield Contact - Siemens SIMATIC ET 200S Manual

Distributed i/o system
Hide thumbs Also See for SIMATIC ET 200S:
Table of Contents

Advertisement

Installation

Installing the shield contact

1. Push the shield contact element onto the first terminal module from below.
2. Push the shield contact element onto the last terminal module from below.
In order to achieve stability of the conductor rail between two shield contact
elements during installation, you must connect an additional shield contact
element after every sixth terminal module (given a width of 15 mm).
3. Saw off the correct length from the conductor rail. The length of the conductor
rail should be: the distance between the shield contact elements + 45 mm.
4. Push the conductor rail into the shield contact element. After installation, the
conductor rail must protrude from the shield contact element by 15 mm on the
left or right.
5. Attach the shield terminals on the conductor rail (between the shield contact
elements).
6. Attach the ground connection terminal to the protruding conductor rail.
Figure 4-7
4-12
Conductor rail
Ground connection terminal
Installing the shield contact
Shield terminals
Shield contact elements
ET 200S Distributed I/O System
EWA-4NEB780602402-09