Commissioning and Diagnostics
6.3
Diagnostics using LEDs
ET 200S Power Supply
Figure 6-6
Status and error displays by means of LEDs on the ET 200S Power Supply
Table 6-6
Status and error displays of the ET 200S Power Supply
UE
UE:
P24V
P24V: Green
I>
I>:
LEDs
UE
P24V
I>
Off
*
*
On
*
*
On
On
Off
On
On
On
On
Off
On
On
Off
Off
*
Not applicable
6-12
LEDs on the ET 200S Power Supply
Green
Yellow
Meaning
No mains voltage
Mains voltage present
Normal operation
Overload: U
> U
A
Amin
Overload: U
< U
A
Amin
Short circuit or
slide switch on standby
Input voltage (green)
Ue
P24V
Output voltage (green)
I>
Overload (yellow)
= On:
Output voltage is switched on
= Standby:
Output voltage is switched off
What to do
Check mains voltage
–
–
Avoid additional loading
Correct overload
Remove short circuit,
put slide switch into On position*
ET 200S Distributed I/O System