5.2.7

Status displays

A binary vector can be switched to the actual value display V24 [SHIFT + V12]
using key V23 [SHIFT + V11]. This allows internal drive converter statuses to be
visualized using the operator panel.
The following signals can be selected using key V23. The actual values of the
selected signals can be visualized in V24.
Guideline:
The drive converter executes the commands available at the power-on logic in
control words 1 and 2. These control words are listed in function package I/O (refer
to Fig. 4.1) The command sources for the individual control word bits are also
defined in function package I/O.
V23 input value = 1
V24 actual value =
ON / OFF 1 (a log. 1
OFF2 (a log.1
OFF3 (a log. 1
Inverter enable (a log. 1
Ramp-function generator enable (a log. 1
Ramp-function generator hold (a log. 1
Setpoint enable (a log. 1
Acknowledge (a log. 1
Inching (a log. 1
Free
Control from the automation system (a log. 1
system)
Clockwise rotating field selection (a log. 1
Counter-clockwise rotating field selection (a log. 1
Motorized potentiometer, raise (a log. 1
potentiometer)
Motorized potentiometer, lower (a log. 1
potentiometer)
External fault (a log. 1
98
All signals are high-active (log 1
Exceptions are specifically referred to.
the ON command)
the OFF2 command)
the OFF3 command)
inverter enable)
setpoint enable)
acknowledge command; 1 s pulse)
inching command)
fault)
the command/status is present).
at the power-on logic
RFG enable)
RFG hold)
control from the automation
CRF)
CCRF)
command, raise motorized
command, lower motorized