Parameterizing The Circuit-Breaker - Siemens SIMOVERT MV Series Commissioning Instructions

Medium-voltage converters with hv-igbt and ihv filter
Table of Contents

Advertisement

4.2.8

Parameterizing the circuit-breaker

Depending on the circuit-breaker, parameterization must be realized in the ULS
function package. This function package is used to define whether the circuit-
breaker is controlled using a pulse- or continuous signal. The pulse- and
monitoring times are defined here. When testing, the circuit-breaker should be
controlled without the system being connected to the main line supply; in this case,
the pre-charging can be simultaneously tested (also refer to Section 4.2.9).
The circuit-breaker must be equipped with an undervoltage trip. This undervoltage
trip ensures that the drive converter is shutdown, wire-breakage proof (fail safe).
The drive converter processes the following signals:
♦ OPEN checkback signal from the circuit-breaker
♦ OPEN checkback signal, leading contact from the circuit-breaker
♦ CLOSE- and OPEN commands to the circuit-breaker
The signals are connected at terminal strip X100.
X100:A15/15C checkback signal, circuit-breaker OPEN
X100:A14/14C checkback signal, leading contact, circuit-breaker OPEN
A80.I / P268
Select negation, checkback signal circuit-breaker
OPEN
B15.I / P269
Select, checkback signal circuit-breaker
SW(0) / HW(1)
B30.X / P274
Circuit-breaker monitoring, closing time
B40.X / P275
Circuit-breaker monitoring, opening time
B20.TRE / P270
Circuit-breaker inhibit time after CLOSE
B20.TRA / P271
Circuit-breaker inhibit time after OPEN
B20.TSE / P272
Circuit-breaker pulse time CLOSE
B20.TSA / P273
Circuit-breaker pulse time, OPEN
B50.I / P276
Select circuit-breaker CLOSE command,
continuous/pulse signal
B80.I / P278
Select circuit-breaker open command, continuous-
/pulse signal
B70.I / P277
Select negation, circuit-breaker CLOSE
B100.I / P279
Select negation, circuit-breaker OPEN
C50.I / P280
Select negation, checkback signal circuit-breaker,
leading contact
C70.I / P281
Select continuous/pulse signal checkback signal
circuit-breaker, leading contact
Siemens AG
6SE8004-0BH76
SIMOVERT MV
Commissioning Instructions
0
0
900 ms
900 ms
100 ms
100 ms
2 s
2 s
1
1
0
0
1
0
53