Status Indication By Means Of Leds; Meaning Of The Leds - Siemens SIMATIC EM 148-FC Manual

Frequency converter
Table of Contents

Advertisement

Commissioning and Diagnostics
3.5

Status indication by means of LEDs

The Frequency Converter frequency converter has three LEDs for indicating
statuses and fault statuses.
Warning
!
The LEDs are electronically controlled. If there is no voltage supplied to the
electronic components and sensors, the LEDs do not light up. However, the power
unit might still be receiving power.
Table 3-2
Labeling
SF
STAT
PWR
This means the following status indications to the DESINA specification are
possible:
Table 3-3
"SF"
LED
Off
Off
On
On
Off
3-6

Meaning of the LEDs

Color
Red
Group error of the Frequency Converter
Yellow
Status of the motor circuit
Green
Status of the power supply (intermediate circuit)
This LED continues to be illuminated after the power
supply has been switched off until the capacitors of the
intermediate circuit have been discharged to under 400 V.

Status indication by means of LEDs

"STAT"
"PWR"
LED
LED
Off
On
Power supply (power unit) present, motor off
On
On
Power supply (power unit) present, motor on (irrespective
of direction)
Off
On
Load voltage not present or Frequency Converter fault,
motor off
Off
Off
Power supply (power unit) not present, motor off
Off
Off
Supply voltage to the electronic components and sensors
is missing (see warning)
Description
Description
EM 148-FC Frequency Converter
A5E00065321-03