Automation Interface - Siemens SIMOVERT MV Series Commissioning Instructions

Medium-voltage converters with hv-igbt and ihv filter
Table of Contents

Advertisement

2.3.2

Automation interface

The automation interface is at slot X03 on board CS7. Slot X03 has an interface
module SS52 (Order No.: 6DD1688-0AE2).
This module supports Profibus SINEC L2 DP.
Automation unit
Fig. 2.1
Maximum permissible cable lengths for the SINEC L2 DP bus cable (Order No.:
6VX1830-0AH10, 6VX1830-0BH10, 6VX1830-3AH10, 6VX1830-3BH10,
6VX1830-3CH10):
9.6 to 187.5 kbaud
500 kbaud
1.5 Mbaud
3 - 12 Mbaud
24
SINEC L2 DP
bus cable
Connecting the automation unit to the CS7 board
max. 1000 m
max. 400 m
max. 200 m
max. 100 m
SIMOVERT MV
SIMADYN D subrack
S01
S07
CS7
X03
Siemens AG
SIMOVERT MV
Connector SM5
Order No.: 6DD1680-0AF0
6SE8004-0BH76
Commissioning Instructions