Installation - Siemens SIMOVERT MV Series Commissioning Instructions

Medium-voltage converters with hv-igbt and ihv filter
Table of Contents

Advertisement

1.3

Installation

The equipment is installed after it has been unpacked and checked to see that the
shipment is complete and not been damaged during transport.
Safe operation of the equipment assumes that it has been installed and
commissioned professionally by qualified personnel taking into account the
warning information in this Instruction Manual.
It is especially important, that the general and national installation- and safety
regulations for working on power equipment are observed. This also includes the
professional use of tools and the use of personnel protection devices and
equipment in the appropriate regulations.
Death, severe bodily injury or significant material damage could result if these
instructions are not observed.
The units are suitable for mounting in enclosed electrical equipment rooms (EN
50178 / 1997, VDE 0160). They should be mounted in dry and dust-free rooms.
The air drawn-in must be free of aggressive gases. If these specified conditions
cannot be fulfilled, then the air drawn into the installation room must be cleaned
using filters, or, for dust-laden air by using filter elements in front of the air mesh of
the cabinet doors.
The ambient drive converter conditions in the equipment rooms may not exceed
the values, specified in Class 3K3 acc. to IEC 721-3-3. The equipment must be de-
rated (reduced output) for temperatures > 40 °C and installation altitudes
> 1000 m.
The standard drive converters conform to degree of protection IP20 (air-cooled) or
IP23 (water-cooled) acc. to DIN VDE 0470 and EN 60529.
The equipment is designed for floor mounting. Four holes for M12 bolts are
provided in each cabinet element which are then used to retain them to the
foundation.
In order to simplify mounting and installation or subsequent change of location, we
recommend that a minimum clearance of 600 mm is kept to the wall.
The clearance between the top of the drive converter and the ceiling must be at
least 650 mm due to the pressure equalization flaps.
The air to cool the power module is drawn-in through the cooling mesh in the
cabinet doors, and the hot air is discharged upwards. Air can be drawn-in through
the false floors, air ducts etc.
12
Siemens AG
SIMOVERT MV
Commissioning Instructions