gefran SIEIDrive ADV50 Series Quick Start-Up page 69

V/f & sensorless vector ac drive
Table of Contents

Advertisement

Available languages

Available languages

Fault
Fault Descriptions
Name
Overload 1
Internal electronic overload trip
Overload 2
Motor overload.
CC (current clamp)
OV hardware error
GFF hardware error
OC hardware error
External Base Block.
(Refer to Pr. 08.07)
Over-current during
acceleration
External Fault
Over-current during
deceleration
Over-current during steady
state operation
Internal EEPROM can not be
programmed.
Internal EEPROM can not be
programmed.
Italiano
1.
Check for possible motor overload.
2.
Check electronic thermal overload setting.
3.
Use a higher power motor.
4.
Reduce the current level so that the drive
output current does not exceed the value set by
the Motor Rated Current Pr.07.00.
1.
Reduce the motor load.
2.
Adjust the over-torque detection setting to an
appropriate setting (Pr.06.03 to Pr.06.05).
Please contact the Gefran Technical Assistance.
1.
When the external input terminal (B.B) is active,
the AC motor drive output will be turned off.
2.
Deactivate the external input terminal (B.B) to
operate the AC motor drive again.
1.
Short-circuit at motor output: Check for possible
poor insulation at the output lines.
2.
Torque boost too high: Decrease the torque
compensation setting in Pr.07.02.
3.
Acceleration Time too short: Increase the
Acceleration Time.
4.
AC motor drive output power is too small:
Replace the AC motor drive with the next
higher power model.
1.
When multi-function input terminals (MI3-MI9)
are set to external fault, the AC motor drive
stops output U, V and W.
2.
Give RESET command after fault has been
cleared.
1.
Short-circuit at motor output: Check for possible
poor insulation at the output line.
2.
Deceleration Time too short: Increase the
Deceleration Time.
3.
AC motor drive output power is too small:
Replace the AC motor drive with the next
higher power model.
1.
Short-circuit at motor output: Check for possible
poor insulation at the output line.
2.
Sudden increase in motor loading: Check for
possible motor stall.
3.
AC motor drive output power is too small:
Replace the AC motor drive with the next
higher power model.
Please contact the Gefran Technical Assistance.
Please contact the Gefran Technical Assistance.
English
Corrective Actions
ADV50 QS, SW-PW V1.11 / CTL V2.11